132
⎯
6 F 2 S 0 8 4 6
Element
Range
Step Default Remarks
SYN1
Synchronism
check
SY1
θ
5 - 75°
1°
30°
SY1UV
10 - 150 V
1 V
83 V
SY1OV
10 - 150 V
1 V
51 V
OVB
10 - 150 V
1 V
51 V
Live bus check
UVB
10 - 150 V
1 V
13 V
Dead bus check
OVL1
10 - 150 V
1 V
51 V
Live line check
UVL1
10 - 150 V
1 V
13 V
Dead line check
TSYN1
0.01 - 10.00 s
0.01 s
1.00 s
Synchronism check time
TLBD1
0.01 - 1.00 s
0.01 s
0.05 s
Voltage check time
TDBL1
0.01 - 1.00 s
0.01 s
0.05 s
Voltage check time
T3PLL
0.01 - 1.00 s
0.01 s
0.05 s
Three phase live line check
TW1
0.1 - 10.0 s
0.1 s
0.2 s
Reclosing signal output time
TS2
5.0 - 300.0 s
0.1 s
20.0 s
Second shot dead time
TS3
5.0 - 300.0 s
0.1 s
20.0 s
Third shot dead time
TS4
5.0 - 300.0 s
0.1 s
20.0 s
Fourth shot dead time
TS2R
5.0 - 300.0 s
0.1 s
30.0 s
Second shot reset time
TS3R
5.0 - 300.0 s
0.1 s
30.0 s
Third shot reset time
TS4R
5.0 - 300.0 s
0.1 s
30.0 s
Fourth shot reset time
ARC - M
Disabled/SPAR/TPAR/
SPAR & TPAR/EXT1P/EXT3P
SPAR & TPAR Autoreclose mode
ARC - DEF
OFF/ON
OFF
DEF autoreclose
ARC-BU
OFF/ON
OFF
Backup trip autoreclose
ARC-EXT OFF/ON
OFF
External
start
ARC - SM
OFF/S2/S3/S4
OFF
Multi - shot autoreclose mode
ARC-SUC
OFF/ON
OFF
Autoreclose success checking
VCHK OFF/LB/DB/SY
LB
Energizing
direction
VTPHSEL
A/B/C
A
Phase of reference voltage
VT - RATE
PH/G / PH/PH
PH/G
VT rating
3PH - VT
BUS/LINE
LINE
Location of three - phase VTs
[UARCSW] P1/P2/P3
(P1)(
∗
)
User ARC switch for PLC
(
∗
)
If this switch is not used for PLC setting, it is invalid.
“VT” is VT ratio setting of distance protection, and “VTs1” is VT ratio setting of a reference
voltage input for voltage and synchronism check element as shown in Figure 2.6.3.1.
In a voltage setting, set “SY1UV”, “SY1OV”, “OVB”, “UVB”, “OVL1” and “UVL1” based on
the VT rating for voltage and synchronism check. (When a voltage rating between line VT and
busbar VT is different as shown in Figure 2.6.3.1, the voltage input from “VT” is matched to the
rating of “VTs1” using the setting of “VT” and “VTs1”.)
CB
Line VT
Busbar VT
VT setting
GRZ100
Busbar
Line
VL
X
VTs1 setting
VB
Reference voltage
for voltage and
synchronism check
For distance
protection
Figure 2.6.3.1 VT and VTs1 Ratio Setting for Busbar or Line Voltage
Содержание GRZ100 B Series
Страница 264: ... 263 6 F 2 S 0 8 4 6 Appendix A Block Diagram ...
Страница 271: ... 270 6 F 2 S 0 8 4 6 ...
Страница 272: ... 271 6 F 2 S 0 8 4 6 Appendix B Signal List ...
Страница 307: ... 306 6 F 2 S 0 8 4 6 ...
Страница 308: ... 307 6 F 2 S 0 8 4 6 Appendix C Variable Timer List ...
Страница 310: ... 309 6 F 2 S 0 8 4 6 Appendix D Binary Input Output Default Setting List ...
Страница 321: ... 320 6 F 2 S 0 8 4 6 ...
Страница 322: ... 321 6 F 2 S 0 8 4 6 Appendix E Details of Relay Menu and LCD Button Operation ...
Страница 331: ... 330 6 F 2 S 0 8 4 6 ...
Страница 340: ... 339 6 F 2 S 0 8 4 6 Appendix G Typical External Connections ...
Страница 377: ... 376 6 F 2 S 0 8 4 6 ...
Страница 384: ... 383 6 F 2 S 0 8 4 6 Appendix J Return Repair Form ...
Страница 388: ... 387 6 F 2 S 0 8 4 6 Customer Name Company Name Address Telephone No Facsimile No Signature ...
Страница 389: ... 388 6 F 2 S 0 8 4 6 ...
Страница 390: ... 389 6 F 2 S 0 8 4 6 Appendix K Technical Data ...
Страница 401: ... 400 6 F 2 S 0 8 4 6 ...
Страница 402: ... 401 6 F 2 S 0 8 4 6 Appendix L Symbols Used in Scheme Logic ...
Страница 405: ... 404 6 F 2 S 0 8 4 6 ...
Страница 406: ... 405 6 F 2 S 0 8 4 6 Appendix M Example of Setting Calculation ...
Страница 417: ... 416 6 F 2 S 0 8 4 6 ...
Страница 418: ... 417 6 F 2 S 0 8 4 6 Appendix N IEC60870 5 103 Interoperability and Troubleshooting ...
Страница 430: ... 429 6 F 2 S 0 8 4 6 Appendix O Programmable Reset Characteristics and Implementation of Thermal Model to IEC60255 8 ...
Страница 434: ... 433 6 F 2 S 0 8 4 6 Appendix P Inverse Time Characteristics ...
Страница 437: ... 436 6 F 2 S 0 8 4 6 ...
Страница 438: ... 437 6 F 2 S 0 8 4 6 Appendix Q Failed Module Tracing and Replacement ...
Страница 444: ... 443 6 F 2 S 0 8 4 6 Appendix R Ordering ...
Страница 447: ......