Phase angle check:
•
Set
Va and Vs1 to any value between the SY1OV and SY1UV settings keeping Va in-phase
with Vs1. Then the SYN1 element operates.
•
Shift the angle of Vs1 from that of Va, and measure the angle at which the element resets.
•
Check that the measured angle is within
±
5° of the SY1
θ
setting. (The default setting of SY1
θ
is 30°.)
•
Change
Va and Vs1, and repeat the above.
Synchronism check element SYN2
•
Apply a single-phase rated voltage to terminal 17 and 18 as shown with broken lines in Figure
6.5.1.7 and set the scheme switch [3PH-VT] to "Line". The test can be performed taking the
same step as testing SYN1.
6.5.1.11 Current Change Detection Elements OCD and OCDP
The test circuit is shown in Figure 6.5.1.8.
Single-phase
current
source
A
TB1
DC
voltmeter
TB4
-1
-2
-A16
-A17
E
GRZ100
DC
power
supply
+
−
Monitoring
jack
A
0V
Figure 6.5.1.8 Testing Current Change Detection Element
The output signal number of the OCD and OCDP is as follows:
Measuring element
Signal number
OCD-A 63
OCD-B 64
OCD-C 65
OCDP-A 357
OCDP-B 358
OCDP-C 359
Operation must be verified by abruptly changing the test current from 0 A to 1.2
×
Setting value or
vice versa.
OCD has a fixed setting of 0.5 A and 0.1 A for 5 A rating and 1 A rating respectively.
6.5.1.12 Level Detectors OCH, OC, EF, EFL, OVG, UVLS and UVLG, UVFS and UVFG, OCBF
Voltage or current level detectors are tested by applying voltage or current individually. A
Содержание GRZ100 B Series
Страница 264: ... 263 6 F 2 S 0 8 4 6 Appendix A Block Diagram ...
Страница 271: ... 270 6 F 2 S 0 8 4 6 ...
Страница 272: ... 271 6 F 2 S 0 8 4 6 Appendix B Signal List ...
Страница 307: ... 306 6 F 2 S 0 8 4 6 ...
Страница 308: ... 307 6 F 2 S 0 8 4 6 Appendix C Variable Timer List ...
Страница 310: ... 309 6 F 2 S 0 8 4 6 Appendix D Binary Input Output Default Setting List ...
Страница 321: ... 320 6 F 2 S 0 8 4 6 ...
Страница 322: ... 321 6 F 2 S 0 8 4 6 Appendix E Details of Relay Menu and LCD Button Operation ...
Страница 331: ... 330 6 F 2 S 0 8 4 6 ...
Страница 340: ... 339 6 F 2 S 0 8 4 6 Appendix G Typical External Connections ...
Страница 377: ... 376 6 F 2 S 0 8 4 6 ...
Страница 384: ... 383 6 F 2 S 0 8 4 6 Appendix J Return Repair Form ...
Страница 388: ... 387 6 F 2 S 0 8 4 6 Customer Name Company Name Address Telephone No Facsimile No Signature ...
Страница 389: ... 388 6 F 2 S 0 8 4 6 ...
Страница 390: ... 389 6 F 2 S 0 8 4 6 Appendix K Technical Data ...
Страница 401: ... 400 6 F 2 S 0 8 4 6 ...
Страница 402: ... 401 6 F 2 S 0 8 4 6 Appendix L Symbols Used in Scheme Logic ...
Страница 405: ... 404 6 F 2 S 0 8 4 6 ...
Страница 406: ... 405 6 F 2 S 0 8 4 6 Appendix M Example of Setting Calculation ...
Страница 417: ... 416 6 F 2 S 0 8 4 6 ...
Страница 418: ... 417 6 F 2 S 0 8 4 6 Appendix N IEC60870 5 103 Interoperability and Troubleshooting ...
Страница 430: ... 429 6 F 2 S 0 8 4 6 Appendix O Programmable Reset Characteristics and Implementation of Thermal Model to IEC60255 8 ...
Страница 434: ... 433 6 F 2 S 0 8 4 6 Appendix P Inverse Time Characteristics ...
Страница 437: ... 436 6 F 2 S 0 8 4 6 ...
Страница 438: ... 437 6 F 2 S 0 8 4 6 Appendix Q Failed Module Tracing and Replacement ...
Страница 444: ... 443 6 F 2 S 0 8 4 6 Appendix R Ordering ...
Страница 447: ......