Section 3 – SR-2 Software Description
OptiSet Global Features
The global features listed below affect all other
OptiSet ranges and settings. If any of these are
changed, all existing OptiSet programmable features
are returned to the default settings.
•
Temperature
Units
•
Setpoint Low Limit
•
Setpoint High Limit
•
Fresh Frozen Range
Temperature Units
Micro Rev
All
HMI Rev
All
Choices
Fahrenheit or Celsius
Factory Set
Fahrenheit
Exceptions
Description
Displays temperatures in either
degrees Fahrenheit or Celsius (Centigrade). Due to
scaling and rounding errors, the math used for
temperature conversion can result in range overlap,
so changing this feature will reset all OptiSet range
values to default.
Setpoint Low Limit
Micro Rev
All
HMI Rev
All
Choices
From -30°F (-36°C) to the setting of
Setpoint High Limit
Factory Set
-20°F (-29°C)
Exceptions
Description
This value allows the lower limit
setpoint to be set as low as -30°F (-36°C) or as high
as the value of Setpoint High Limit. If Setpoint Low
Limit = Setpoint High Limit only that single setpoint is
available. Changing this feature will reset all OptiSet
range values to default.
Setpoint temperatures less than -25°F (-32°C)
should only be used when absolutely required by the
load.
Setpoint High Limit
Micro Rev
HMI Rev
All
Choices
From 90°F (32°C) to the setting of
Setpoint Low Limit
Factory Set
80°F (27°C)
Exceptions
Description
This feature allows the upper limit
setpoint to be set as high as 90°F (32°C) or as low
as the value of Setpoint Low Limit. If Setpoint High
Limit = Setpoint Low Limit only that single setpoint is
available. Changing this feature will reset all OptiSet
range values to default.
Fresh Frozen Range
Micro Rev
All
HMI Rev
All
Choices
24°F (-4°C) or 15°F (-9°C)
Factory Set
24°F (-4°C)
Exceptions
Description
One set of general control
specifications is used when operating in the Fresh
range, and another set of general operating
specifications is used when operating in the Frozen
range. This feature allows the line between Fresh
and Frozen ranges to be selected as either 15°F (-
9°C) or 24°F (-4°C). All setpoints less than or equal
to this value will be treated as frozen ranges. All
setpoints greater than this value will be treated as
Fresh ranges.
When programming OptiSet, no range may include
both Frozen and Fresh range setpoints. This value
is the high value of the last frozen range
programmed. The next range programmed will start
at this value + 1-degree depending on the selection
made above. Changing this feature will reset all
OptiSet range values to default.
3-26
31 January 2005
Содержание SR-2 SmartReefer2
Страница 4: ......
Страница 7: ...Tab goes here and the next page should be GREEN Section 1 Safety...
Страница 8: ......
Страница 10: ...Section 1 SR 2 Safety Information 1 2 18 January 2005...
Страница 14: ...Section 1 SR 2 Safety Information 1 6 18 January 2005...
Страница 15: ...Tab goes here and the next page should be GREEN Section 2 Hardware Description...
Страница 16: ......
Страница 48: ...Section 2 SR 2 Hardware Description 2 32 31 January 2005...
Страница 49: ...Tab goes here and the next 2 pages should be GREEN Section 3 Software Description...
Страница 50: ......
Страница 96: ...Section 3 SR 2 Software Description 3 46 31 January 2005...
Страница 97: ...Tab goes here and the next page should be GREEN Section 4 Operation...
Страница 98: ......
Страница 181: ...Tab goes here and the next 2 pages should be GREEN Section 5 Diagnostics...
Страница 182: ......
Страница 266: ...Section 5 SR 2 Diagnostics 5 84 02 February 2005...
Страница 267: ...Tab goes here and the next page should be GREEN Section 6 Service Procedures...
Страница 268: ......
Страница 270: ...Section 6 SR 2 Service Procedure Index Page 2 01 February 2005...
Страница 282: ...Section 6 SR 2 Service Procedure A01B Page 6 P41RA01B 31 January 2005...
Страница 298: ...Section 6 SR 2 Service Procedure A02A Page 12 P41RA02A 02 February 2005...
Страница 318: ...Section 6 SR 2 Service Procedure A03B Page 4 P41RA03B 30 January 2005...
Страница 338: ...Section 6 SR 2 Service Procedure A15A Page 4 P41RA15A 30 January 2005...
Страница 360: ...Section 6 SR 2 Service Procedure A46B Page 8 P41RA46B 30 January 2005...
Страница 366: ...Section 6 SR 2 Service Procedure A48A Page 6 P41RA48A 30 January 2005...
Страница 376: ...Section 6 SR 2 Service Procedure A50A Page 6 P41RA50A 31 January 2005...
Страница 394: ...Section 6 SR 2 Service Procedure F08A Page 4 P41RF08A 30 January 2005...
Страница 398: ...Section 6 SR 2 Service Procedure F09A Page 4 P41RF09A 30 January 2005...
Страница 402: ...Section 6 SR 2 Service Procedure G03A Page 4 P41RG03A 31 January 2005...
Страница 406: ...Section 6 SR 2 Service Procedure H04A Page 4 P41RH04A 30 January 2005...
Страница 407: ...Tab goes here and the next page should be GREEN Section 7 Service Information...
Страница 408: ......
Страница 410: ...Section 7 SR 2 Information 7 2 02 February 2005...
Страница 419: ...Tab goes here and the next page should be GREEN Section 8 Schematics and Wiring Diagrams...
Страница 420: ......
Страница 422: ...Section 8 SR 2 Drawings 8 2 01 February 2005...
Страница 424: ...Section 8 SR 2 Drawings 8 4 01 February 2005...
Страница 425: ...8 5...
Страница 426: ...8 6...
Страница 427: ...8 7...
Страница 428: ...8 8...
Страница 429: ...8 9...
Страница 430: ...8 10...
Страница 431: ...8 11...