Section 3 – SR-2 Software Description
Economy Mode OptiSet Features - Both
Frozen and Fresh Ranges
The only features that can be modified in Economy
Mode operation are door switch operation. All other
values are relaxed but fixed values and cannot be
changed.
Cycle Sentry Door Open Forces
Micro Rev
All
HMI Rev
All
Choices
Off or Log Only
Factory Set
Log Only
Exceptions
Only if Cycle Sentry mode is turned
on for the range.
Description
If the optional door switch is
installed this feature allows the Door Open action for
the selected range to be set. If this feature is set
OFF the unit will shut the unit down and log the door
opening 4 seconds after the door is opened. If the
unit is in defrost when the door is opened the defrost
cycle will be completed before the unit shuts down.
If this feature is set LOG ONLY the door opening will
be logged after 4 seconds but the unit will continue
to run.
Door openings are logged in both the CargoWatch
and ServiceWatch data loggers. The door switch
must be open or closed for 4 seconds before the
event is logged to prevent false readings.
Cycle Sentry Door Open Timeout
Micro Rev
All
HMI Rev
All
Choices
Off, 1 hour to 4 hours in 10minute
increments
Factory Set
Off
Exceptions
Only appears if Cycle Sentry Door
Open Forces = Off.
Description
This feature allows the unit to restart
if the door open time exceeds the set limit.
Door Open Timeout for the selected range can be
set to Off or to a time limit from 1 to 4 hours, in 10-
minute increments. If set Off the unit will remain off
until the door is closed. If a time period is selected
the unit will restart and run 4 seconds after the time
period elapses. It will continue to run even if the
door is still open.
Continuous Door Open Forces
Micro Rev
All
HMI Rev
All
Choices
Off or Log Only
Factory Set
Log Only
Exceptions
Only if Continuous mode is turned
on for the range.
Description
If the optional door switch is
installed this feature allows the Door Open action for
the selected range to be set. If this feature is set
OFF the unit will shut the unit down and log the door
opening 4 seconds after the door is opened. If the
unit is in defrost when the door is opened the defrost
cycle will be completed before the unit shuts down.
If this feature is set LOG ONLY the door opening will
be logged after 4 seconds but the unit will continue
to run.
Door openings are logged in both the CargoWatch
and ServiceWatch data loggers. The door switch
must be open or closed for 4 seconds before the
event is logged to prevent false readings.
Continuous Door Open Timeout
Micro Rev
All
HMI Rev
All
Choices
Off, 1 hour to 4 hours in 10minute
increments
Factory Set
Off
Exceptions
Only appears if Continuous Door
Open Forces = Off.
Description
This feature allows the unit to restart
if the door open time exceeds the set limit.
Door Open Timeout for the selected range can be
set to Off or for a time limit from 1 to 4 hours, in 10-
minute increments. If set Off the unit will remain off
until the door is closed. If a time period is selected
the unit will restart and run 4 seconds after the time
period elapses. It will continue to run even if the
door is still open.
3-30
31 January 2005
Содержание SR-2 SmartReefer2
Страница 4: ......
Страница 7: ...Tab goes here and the next page should be GREEN Section 1 Safety...
Страница 8: ......
Страница 10: ...Section 1 SR 2 Safety Information 1 2 18 January 2005...
Страница 14: ...Section 1 SR 2 Safety Information 1 6 18 January 2005...
Страница 15: ...Tab goes here and the next page should be GREEN Section 2 Hardware Description...
Страница 16: ......
Страница 48: ...Section 2 SR 2 Hardware Description 2 32 31 January 2005...
Страница 49: ...Tab goes here and the next 2 pages should be GREEN Section 3 Software Description...
Страница 50: ......
Страница 96: ...Section 3 SR 2 Software Description 3 46 31 January 2005...
Страница 97: ...Tab goes here and the next page should be GREEN Section 4 Operation...
Страница 98: ......
Страница 181: ...Tab goes here and the next 2 pages should be GREEN Section 5 Diagnostics...
Страница 182: ......
Страница 266: ...Section 5 SR 2 Diagnostics 5 84 02 February 2005...
Страница 267: ...Tab goes here and the next page should be GREEN Section 6 Service Procedures...
Страница 268: ......
Страница 270: ...Section 6 SR 2 Service Procedure Index Page 2 01 February 2005...
Страница 282: ...Section 6 SR 2 Service Procedure A01B Page 6 P41RA01B 31 January 2005...
Страница 298: ...Section 6 SR 2 Service Procedure A02A Page 12 P41RA02A 02 February 2005...
Страница 318: ...Section 6 SR 2 Service Procedure A03B Page 4 P41RA03B 30 January 2005...
Страница 338: ...Section 6 SR 2 Service Procedure A15A Page 4 P41RA15A 30 January 2005...
Страница 360: ...Section 6 SR 2 Service Procedure A46B Page 8 P41RA46B 30 January 2005...
Страница 366: ...Section 6 SR 2 Service Procedure A48A Page 6 P41RA48A 30 January 2005...
Страница 376: ...Section 6 SR 2 Service Procedure A50A Page 6 P41RA50A 31 January 2005...
Страница 394: ...Section 6 SR 2 Service Procedure F08A Page 4 P41RF08A 30 January 2005...
Страница 398: ...Section 6 SR 2 Service Procedure F09A Page 4 P41RF09A 30 January 2005...
Страница 402: ...Section 6 SR 2 Service Procedure G03A Page 4 P41RG03A 31 January 2005...
Страница 406: ...Section 6 SR 2 Service Procedure H04A Page 4 P41RH04A 30 January 2005...
Страница 407: ...Tab goes here and the next page should be GREEN Section 7 Service Information...
Страница 408: ......
Страница 410: ...Section 7 SR 2 Information 7 2 02 February 2005...
Страница 419: ...Tab goes here and the next page should be GREEN Section 8 Schematics and Wiring Diagrams...
Страница 420: ......
Страница 422: ...Section 8 SR 2 Drawings 8 2 01 February 2005...
Страница 424: ...Section 8 SR 2 Drawings 8 4 01 February 2005...
Страница 425: ...8 5...
Страница 426: ...8 6...
Страница 427: ...8 7...
Страница 428: ...8 8...
Страница 429: ...8 9...
Страница 430: ...8 10...
Страница 431: ...8 11...