
Functional Description
65
Reference control [214]
To control the speed of the motor, the VSD needs a ref-
erence signal. This reference signal can be controlled
by a remote source from the installation, the keyboard
of the VSD, or by serial or fieldbus communication.
Select the required reference control for the application
in this menu
.
Communication information
Run/Stop Control [215]
This function is used to select the source for run and
stop commands. Start/stop via analogue signals can
be achieved by combining a few functions. This is
described in the Chapter 7. page 33.
Communication information
Reset Contmrol [216]
When the VSD is stopped due to a failure, a reset com-
mand is required to make it possible to restart the VSD.
Use this function to select the source of the reset sig-
nal.
Communication information
Local/Remote key function [217]
The Toggle key on the keyboard, see section 9.2.5,
page 52, has two functions and is activated in this
menu. As default the key is just set to operate as a Tog-
gle key that moves you easily through the menus in the
toggle loop. The second function of the key allows you
to easily swap between Local and normal operation (set
up via [214] and [215]) of the VSD. Local mode can
Default:
Remote
Remote
0
The reference signal comes from the ana-
logue inputs of the terminal strip (terminals
1-22).
Keyboard
1
Reference is set with the + and - keys on
the Control Panel. Can only be done in
menu Set/View reference [310].
Com
2
The reference is set via the serial commu-
nication (RS 485, Fieldbus.) See section
section 10.5 for further information.
Option
3
The reference is set via an option. Only
available if the option can control the refer-
ence value.
NOTE: If the reference is switched from Remote to
Keyboard, the last remote reference value will be the
default value for the control panel.
Modbus Instance no/DeviceNet no:
43014
Profibus slot/index
168/173
Fieldbus format
UInt
Modbus format
UInt
Default:
Remote
Remote
0
The start/stop signal comes from the digital
inputs of the terminal strip (terminals 1-22).
Keyboard
1
Start and stop is set on the Control Panel.
Com
2
The start/stop is set via the serial communi-
cation (RS 485, Fieldbus.) See Fieldbus or
RS232/485 option manual for details.
Option
3
The start/stop is set via an option.
Stp
Remote
A
Stp
Remote
A
Modbus Instance no/DeviceNet no:
43015
Profibus slot/index
168/174
Fieldbus format
UInt
Modbus format
UInt
Default:
Remote
Remote
0
The command comes from the inputs of
the terminal strip (terminals 1-22).
Keyboard
1
The command comes from the command
keys of the Control Panel.
Com
2
The command comes from the serial
communication (RS 485, Fieldbus).
Keyb
3
The command comes from the inputs of
the terminal strip (terminals 1-22) or the
keyboard.
Com +
Keyb
4
The command comes from the serial
communication (RS485, Fieldbus) or the
keyboard.
Rem+Keyb
+Com
5
The command comes from the inputs of
the terminal strip (terminals 1-22), the
keyboard or the serial communication
(RS485, Fieldbus).
Option
6
The command comes from an option.
Only available if the option can control
the reset command.
Modbus Instance no/DeviceNet no:
43016
Profibus slot/index
168/175
Fieldbus format
UInt
Modbus format
UInt
Stp
Remote
A
Содержание F33 Series
Страница 1: ...TECO F33 Variable Speed Drive Instruction manual English Software version 4 2X...
Страница 3: ......
Страница 33: ...30 Getting Started...
Страница 51: ...48 Main Features...
Страница 53: ...50 EMC and Machine Directive...
Страница 59: ...56 Operation via the Control Panel...
Страница 65: ...62 Serial communication...
Страница 159: ...156 Troubleshooting Diagnoses and Maintenance...
Страница 165: ...162 Options...
Страница 179: ...176 Technical Data...
Страница 187: ...184 Menu List...