112
Functional Description
With load type Basic, [415], used the Max Alarm Margin
sets the band above the Normal Load, [41B], menu that
does not generate an alarm. With load type Load Curve,
[415], used the Max Alarm Margin sets the band above
the Load Curve, [41C], that does not generate an
alarm. The Max Alarm Margin is a percentage of nomi-
nal motor torque.
Communication information
Max Alarm delay [4162]
Sets the delay time between the first occurrence of max
alarm condition and after when the alarm is given.
Communication information
Max Pre AlarmMargin [4171]
With load type Basic, [415], used the Max Pre-Alarm
Margin sets the band above the Normal Load, [41B],
menu that does not generate a pre-alarm. With load
type Load Curve, [415], used the Max Pre-Alarm Margin
sets the band above the Load Curve, [41C], that does
not generate a pre-alarm. The Max Pre-Alarm Margin is
a percentage of nominal motor torque.
Communication information
Max Pre Alarm delay [4172]
Sets the delay time between the first occurrence of max
pre alarm condition and after when the alarm is given.
Communication information
With load type Basic, [415], used the Min Pre-Alarm
Margin sets the band under the Normal Load, [41B],
menu that does not generate a pre-alarm. With load
type Load Curve, [415], used the Min Pre-Alarm Margin
sets the band under the Load Curve, [41C], that does
not generate a pre-alarm. The Min Pre-Alarm Margin is
a percentage of nominal motor torque
.
Default:
15%
Range:
0–400%
Modbus Instance no/DeviceNet no: 43326
Profibus slot/index
169/230
Fieldbus format
Long, 1=1%
Modbus format
EInt
Default:
0.1 s
Range:
0-90 s
Modbus Instance no/DeviceNet no: 43330
Profibus slot/index
169/234
Fieldbus format
Long, 1=0.1 s
Modbus format
EInt
Stp
15%
A
Stp
0.1s
A
Default:
10%
Range:
0–400%
Modbus Instance no/DeviceNet no: 43327
Profibus slot/index
169/231
Fieldbus format
Long, 1=0.1%
Modbus format
EInt
Default:
0.1 s
Range:
0–90 s
Modbus Instance no/DeviceNet no: 43331
Profibus slot/index
169/235
Fieldbus format
Long, 1=0.1 s
Modbus format
EInt
Default:
10%
Range:
0-400%
Stp
10%
A
Stp
0.1s
A
Stp
10%
A
Содержание F33 Series
Страница 1: ...TECO F33 Variable Speed Drive Instruction manual English Software version 4 2X...
Страница 3: ......
Страница 33: ...30 Getting Started...
Страница 51: ...48 Main Features...
Страница 53: ...50 EMC and Machine Directive...
Страница 59: ...56 Operation via the Control Panel...
Страница 65: ...62 Serial communication...
Страница 159: ...156 Troubleshooting Diagnoses and Maintenance...
Страница 165: ...162 Options...
Страница 179: ...176 Technical Data...
Страница 187: ...184 Menu List...