124
Functional Description
Digital Input 2 [522] to Digital Input 8
[528]
Same function as DigIn 1 [521]. Default function for
DigIn 8 is Reset. For DigIn 3 to 7 the default function is
Off.
Communication information
Additional digital inputs [529] to [52H]
Additional digital inputs with I/O option board installed,
B1 DigIn 1 [529] - B3 DigIn 3 [52H]. B stands for board
and 1 to 3 is the number of the board which is related
to the position of the I/O option board on the option
mounting plate. The functions and selections are the
same as DigIn 1 [521].
Communication information
11.5.3 Analogue Outputs [530]
Submenu with all settings for the analogue outputs.
Selections can be made from application and VSD val-
ues, in order to visualize actual status. Analogue out-
puts can also be used as a mirror of the analogue
input. Such a signal can be used as:
• a reference signal for the next VSD in a Master/
Slave configuration (see Fig. 106).
• a feedback acknowledgement of the received ana-
logue reference value.
AnOut1 Function [531]
Sets the function for the Analogue Output 1. Scale and
range are defined by AnOut1 Advanced settings [533].
Communication information
Table 26
Parameter Set
Set Ctrl 1
Set Ctrl 2
A
0
0
B
1
0
C
0
1
D
1
1
NOTE: To activate the parameter set selection, menu
241 must be set to DigIn.
Default:
RunR
Selection:
Same as in menu
[
]
Modbus Instance no/DeviceNet no: 43241–43248
Profibus slot/index
169/146–169/152
Fieldbus format
UInt
Modbus format
UInt
Modbus Instance no/DeviceNet no: 43501–43509
Profibus slot/index
170/150–170/158
Fieldbus format
Int
Modbus format
Int
Stp
RunR
A
Default:
Speed
Process Val 0
Actual process value according to Proc-
ess feedback signal.
Speed
1
Actual speed.
Torque 2
Actual
torque.
Process Ref 3
Actual process reference value.
Shaft Power 4
Actual shaft power.
Frequency
5
Actual frequency.
Current
6
Actual current.
El power
7
Actual electrical power.
Output volt
8
Actual output voltage.
DC-voltage
9
Actual DC link voltage.
AnIn1
10
Mirror of received signal value on
AnIn1.
AnIn2
11
Mirror of received signal value on
AnIn2.
AnIn3
12
Mirror of received signal value on
AnIn3.
AnIn4
13
Mirror of received signal value on
AnIn4.
NOTE: When selections AnIn1, AnIn2 …. AnIn4 is
selected, the setup of the AnOut (menu [532] or [535])
has to be set to 0-10V or 0-20mA. When the AnOut Setup
is set to e.g. 4-20mA, the mirroring is not working
correct.
Modbus Instance no/DeviceNet no: 43251
Profibus slot/index
169/155
Fieldbus format
UInt
Modbus format
UInt
Stp
Speed
A
Содержание F33 Series
Страница 1: ...TECO F33 Variable Speed Drive Instruction manual English Software version 4 2X...
Страница 3: ......
Страница 33: ...30 Getting Started...
Страница 51: ...48 Main Features...
Страница 53: ...50 EMC and Machine Directive...
Страница 59: ...56 Operation via the Control Panel...
Страница 65: ...62 Serial communication...
Страница 159: ...156 Troubleshooting Diagnoses and Maintenance...
Страница 165: ...162 Options...
Страница 179: ...176 Technical Data...
Страница 187: ...184 Menu List...