Functional Description
115
11.4.2 Process Protection [420]
Submenu with settings regarding protection functions
for the VSD and the motor.
Low Voltage Override [421]
If a dip in the mains supply occurs and the low voltage
override function is enabled, the VSD will automatically
decrease the motor speed to keep control of the appli-
cation and prevent an under voltage trip until the input
voltage rises again. Therefore the rotating energy in the
motor/load is used to keep the DC link voltage level at
the override level, for as long as possible or until the
motor comes to a standstill. This is dependent on the
inertia of the motor/load combination and the load of
the motor at the time the dip occurs, see Fig. 100.
Communication information
Fig. 100 Low voltage override
Rotor locked [422]
With the rotor locked function enabled, the VSD will pro-
tect the motor and application when this is stalled
whilst increasing the motor speed from standstill. This
protection will coast the motor to stop and indicate a
fault when the Torque Limit has been active at very low
speed for more than 5 seconds.
Communication information
Motor lost [423]
With the motor lost function enabled, the VSD is able to
detect a fault in the motor circuit: motor, motor cable,
thermal relay or output filter. Motor lost will cause a
trip, and the motor will coast to standstill, when a miss-
ing motor phase is detected during a period of 5 s.
Communication information
Default:
On
Off
0 At a voltage dip the low voltage trip will protect.
On
1
At mains dip, VSD ramps down until voltage
rises.
Modbus Instance no/DeviceNet no: 43361
Profibus slot/index
170/10
Fieldbus format
UInt
Modbus format
UInt
NOTE: During the low voltage override the LED trip/limit
blinks.
Stp
On
A
t
t
(06-F60new)
Override
level
Low Volt.
level
Speed
DC link voltage
Default:
Off
Off
0
No detection
On
1
VSD will trip when locked rotor is detected.
Trip message “Locked Rotor”.
Modbus Instance no/DeviceNet no: 43362
Profibus slot/index
170/11
Fieldbus format
UInt
Modbus format
UInt
Default:
Off
Off
0
Function switched off to be used if no
motor or very small motor connected.
Trip
1
VSD will trip when the motor is discon-
nected. Trip message “Motor Lost”.
Modbus Instance no/DeviceNet no: 43363
Profibus slot/index
170/12
Fieldbus format
UInt
Modbus format
UInt
Stp
Off
A
Stp
Off
A
Содержание F33 Series
Страница 1: ...TECO F33 Variable Speed Drive Instruction manual English Software version 4 2X...
Страница 3: ......
Страница 33: ...30 Getting Started...
Страница 51: ...48 Main Features...
Страница 53: ...50 EMC and Machine Directive...
Страница 59: ...56 Operation via the Control Panel...
Страница 65: ...62 Serial communication...
Страница 159: ...156 Troubleshooting Diagnoses and Maintenance...
Страница 165: ...162 Options...
Страница 179: ...176 Technical Data...
Страница 187: ...184 Menu List...