Functional Description
125
AnOut 1 Setup [532]
Preset scaling and offset of the output configuration
.
Communication information
Fig. 106
AnOut1 Advanced [533]
With the functions in the AnOut1 Advanced menu, the
output can be completely defined according to the
application needs. The menus will automatically be
adapted to “mA” or “V”, according to the selection in
AnOut1 Setup [532].
This parameter is automatically displayed if User mA or
User V is selected in menu AnOut 1 Setup [532]. The
menu will automatically adapt to current or voltage set-
ting according to the selected setup. Only visible if
[532] = User mA/V.
Communication information
This parameter is automatically displayed if User mA or
User V is selected in menu AnOut1 Setup [532]. The
menu will automatically adapt to current or voltage set-
ting according to the selected setup. Only visible if
[532] = User mA/V
.
Communication information
Default:
4-20mA
4–20mA
0
The current output has a fixed threshold
(Live Zero) of 4 mA and controls the full
range for the output signal. See Fig. 103.
0–20mA
1
Normal full current scale configuration of
the output that controls the full range for
the output signal. See Fig. 102.
User mA
2
The scale of the current controlled output
that controls the full range for the output
signal. Can be defined by the advanced
AnOut Min and AnOut Max menus.
User Bipol
mA
3
Sets the output for a bipolar current out-
put, where the scale controls the range
for the output signal. Scale can be
defined in advanced menu AnOut Bipol.
0-10V
4
Normal full voltage scale configuration of
the output that controls the full range for
the output signal. See Fig. 102.
2–10V
5
The voltage output has a fixed threshold
(Live Zero) of 2 V and controls the full
range for the output signal. See Fig. 103.
User V
6
The scale of the voltage controlled output
that controls the full range for the output
signal. Can be defined by the advanced
AnOut Min and AnOut Max menus.
User Bipol V 7
Sets the output for a bipolar voltage out-
put, where the scale controls the range
for the output signal. Scale can be
defined in advanced menu AnOut Bipol.
Modbus Instance no/DeviceNet no: 43252
Profibus slot/index
169/156
Fieldbus format
UInt
Modbus format
UInt
Stp
4-20mA
A
VSD 1
Master
VSD 2
Slave
Ref
.
AnOut
Ref.
Default:
4 mA
Range:
0.00 – 20.00 mA, 0 – 10.00 V
Modbus Instance no/DeviceNet no: 43253
Profibus slot/index
169/157
Fieldbus format
Long, 1=0.01
Modbus format
EInt
Default:
20.00 mA
Range:
0.00–20.00 mA, 0–10.00 V
Modbus Instance no/DeviceNet no: 43254
Profibus slot/index
169/158
Fieldbus format
Long, 1=0.01
Modbus format
EInt
Stp
A
Stp
4mA
A
Stp
20.0mA
Содержание F33 Series
Страница 1: ...TECO F33 Variable Speed Drive Instruction manual English Software version 4 2X...
Страница 3: ......
Страница 33: ...30 Getting Started...
Страница 51: ...48 Main Features...
Страница 53: ...50 EMC and Machine Directive...
Страница 59: ...56 Operation via the Control Panel...
Страница 65: ...62 Serial communication...
Страница 159: ...156 Troubleshooting Diagnoses and Maintenance...
Страница 165: ...162 Options...
Страница 179: ...176 Technical Data...
Страница 187: ...184 Menu List...