22
Control Connections
4.2
Terminal connections
The terminal strip for connecting the control signals is
accessible after opening the front panel.
The table describes the default functions for the sig-
nals. The inputs and outputs are programmable for
other functions as described in chapter 11. page 53.
For signal specifications refer to chapter 14. page 153.
4.3
Inputs configuration
with the switches
The switches S1 to S4 are used to set the input configu-
ration for the 4 analogue inputs AnIn1, AnIn2, AnIn3
and AnIn4 as described in table 15. See Fig. 28 for the
location of the switches
.
NOTE: The maximum total combined current for outputs
11, 20 and 21 is 100mA.
Table 14
Control signals
Terminal
Name
Function (Default)
Outputs
1
+10 V
+10 VDC supply voltage
6
-10 V
-10 VDC supply voltage
7
Common
Signal ground
11
+24 V
+24 VDC supply voltage
12
Common
Signal ground
15
Common
Signal ground
Digital inputs
8
DigIn 1
RunL (reverse)
9
DigIn 2
RunR (forward)
10
DigIn 3
Off
16
DigIn 4
Off
17
DigIn 5
Off
18
DigIn 6
Off
19
DigIn 7
Off
22
DigIn 8
RESET
Digital outputs
20
DigOut 1
Ready
21
DigOut 2
Brake
Analogue inputs
2
AnIn 1
Process Ref
3
AnIn 2
Off
4
AnIn 3
Off
5
AnIn 4
Off
Analogue outputs
13
Speed
Min speed to max speed
14
Torque
0 to max torque
Relay outputs
31
N/C 1
Relay 1 output
Trip, active when the VSD is in a
TRIP condition.
32
COM 1
33
N/O 1
41
N/C 2
Relay 2 output
Run, active when the VSD is
started.
42
COM 2
43
N/O 2
51
COM 3
Relay 3 output
Off
52
N/O 3
NOTE: N/C is opened when the relay is active and N/O is
closed when the relay is active.
Table 15
Switch settings
Input
Signal type
Switch
AnIn1
Voltage
S1
Current (default)
S1
AnIn2
Voltage
S2
Current (default)
S2
AnIn3
Voltage
S3
Current (default)
S3
AnIn4
Voltage
S4
Current (default)
S4
NOTE: Scaling and offset of AnIn1 - AnIn4 can be
configured using the software. See menus [512], [515],
[518] and [51B] in section 11.5, page 106.
NOTE: the 2 analogue outputs AnOut 1 and AnOut 2 can
be configured using the software. See menu [530]
section 11.5.3, page 114
Table 14
Control signals
Terminal
Name
Function (Default)
U
I
U
I
U
I
U
I
U
I
U
I
U
I
U
I
Содержание F33 Series
Страница 1: ...TECO F33 Variable Speed Drive Instruction manual English Software version 4 2X...
Страница 3: ......
Страница 33: ...30 Getting Started...
Страница 51: ...48 Main Features...
Страница 53: ...50 EMC and Machine Directive...
Страница 59: ...56 Operation via the Control Panel...
Страница 65: ...62 Serial communication...
Страница 159: ...156 Troubleshooting Diagnoses and Maintenance...
Страница 165: ...162 Options...
Страница 179: ...176 Technical Data...
Страница 187: ...184 Menu List...