
Functional Description
119
Parameter to set the maximum value of the external
reference signal. Only visible if [512] = User mA/V
.
Communication information
Special function: Inverted reference signal
If the AnIn minimum value is higher than the AnIn maxi-
mum value, the input will act as an inverted reference
input, see Fig. 104.
Fig. 104 Inverted reference
This menu is automatically displayed if AnIn1 Setup is
set to User Bipol mA or User Bipol V. The window will
automatically show mA or V range according to selected
function. The range is set by changing the positive max-
imum value; the negative value is automatically
adapted accordingly. Only visible if [512] = User Bipol
mA/V. The inputs RunR and RunL input need to be
active, and Rotation, [219], must be set to “R+L”, to
operate the bipolar function on the analogue input.
Communication information
AnIn1 Function Min [5134]
With AnIn1 Function Min the physical minimum value is
scaled to selected process unit. The default scaling is
dependent of the selected function of AnIn1 [511].
Table 25 shows corresponding values for the min and
max selections depending on the function of the ana-
logue input [511].
Communication information
AnIn1 Function Value Min [5135]
With AnIn1 Function ValMin you define a user-defined
value for the signal. Only visible when user-defined is
selected in menu [5134].
Default:
10.00 V/20.00 mA
Range:
0.00–20.00 mA
0–10.00 V
Modbus Instance no/DeviceNet no: 43204
Profibus slot/index
169/108
Fieldbus format
Long
Modbus format
EInt
Default:
0.00–10.00 V
Range:
0.0–20.0 mA, 0.00–10.00 V
Stp
10.0V/20.00mA
0
1 0 V
100 %
n
(NG_06-F25)
Invert
Ref
AnIn Min >
AnIn Max
Stp
10.00V
A
Modbus Instance no/DeviceNet no: 43205
Profibus slot/index
169/109
Fieldbus format
Long
Modbus format
EInt
Default:
Min
Min
0
Min value
Max
1
Max value
User-
defined
2
Define user value in menu [5135]
Table 25
AnIn Function
Min
Max
Speed
Min Speed [341]
Torque
0%
Max Torque [351]
Process Ref
Process Min [324]
Process Max [325]
Process Value
Process Min [324]
Process Max [325]
Modbus Instance no/DeviceNet no: 43206
Profibus slot/index
169/110
Fieldbus format
UInt
Modbus format
UInt
Default:
0.000
Range:
-10000.000 – 10000.000
Stp
Min
A
Stp
0.000
A
Содержание F33 Series
Страница 1: ...TECO F33 Variable Speed Drive Instruction manual English Software version 4 2X...
Страница 3: ......
Страница 33: ...30 Getting Started...
Страница 51: ...48 Main Features...
Страница 53: ...50 EMC and Machine Directive...
Страница 59: ...56 Operation via the Control Panel...
Страница 65: ...62 Serial communication...
Страница 159: ...156 Troubleshooting Diagnoses and Maintenance...
Страница 165: ...162 Options...
Страница 179: ...176 Technical Data...
Страница 187: ...184 Menu List...