12. Troubleshooting, Diagnoses and Maintenance
12.1 Trips, warnings and limits
In order to protect the variable speed drive the principal
operating variables are continuously monitored by the
system. If one of these variables exceeds the safety
limit an error/warning message is displayed. In order to
avoid any possibly dangerous situations, the inverter
sets itself into a stop Mode called Trip and the cause of
the trip is shown in the display.
Trips will always stop the VSD. Trips can be divided into
normal and soft trips, depending on the setup Trip Type,
see menu [250] Autoreset. Normal trips are default. For
normal trips the VSD stops immediately, i.e. the motor
coasts naturally to a standstill. For soft trips the VSD
stops by ramping down the speed, i.e. the motor decel-
erates to a standstill.
“Normal Trip”
• The VSD stops immediately, the motor coasts to nat-
urally to a standstill.
• The Trip relay or output is active (if selected).
• The Trip LED is on.
• The accompanying trip message is displayed.
• The “TRP” status indication is displayed (area D of
the display).
“Soft Trip”
• the VSD stops by decelerating to a standstill.
During the deceleration.
• The accompanying trip message is displayed,
including an additional soft trip indicator “S” before
the trip time.
• The Trip LED is blinking.
• The Warning relay or output is active (if selected).
After standstill is reached.
• The Trip LED is on.
• The Trip relay or output is active (if selected).
• The “TRP” status indication is displayed (area D of
the display).
Apart from the TRIP indicators there are two more indi-
cators to show that the inverter is in an “abnormal” sit-
uation.
“Warning”
• The inverter is close to a trip limit.
• The Warning relay or output is active (if selected).
• The Trip LED is blinking.
• The accompanying warning message is displayed in
window [722] Warning.
• One of the warning indications is displayed (area F
of the display).
“Limits”
• The inverter is limiting torque and/or frequency to
avoid a trip.
• The Limit relay or output is active (if selected).
• The Trip LED is blinking.
•
One of the Limit status indications is displayed (area
D of the display)
.
Table 30
List of trips and warnings
Trip/Warning
messages
Selections
Trip
(Normal/
Soft)
Warning
indicators
(Area D)
Motor I
2
t
Trip/Off/Limit
Normal/Soft I
2
t
PTC
Trip/Off
Normal/Soft
Motor lost
Trip/Off
Normal
Locked rotor
Trip/Off
Normal
Ext trip
Via DigIn
Normal/Soft
Ext Mot Temp
Via DigIn
Normal/Soft
Mon MaxAlarm
Trip/Off/Warn
Normal/Soft
Mon MinAlarm
Trip/Off/Warn
Normal/Soft
Comm error
Trip/Off/Warn
Normal/Soft
PT100
Trip/Off
Normal/Soft
Deviation
Via Option
Normal
Pump
Via Option
Normal
Over temp
On
Normal
OT
Over curr F
On
Normal
Over volt D
On
Normal
Over volt G
On
Normal
Over volt
On
Normal
Over speed
On
Normal
Under voltage
On
Normal
LV
Power Fault
On
Normal
Desat
On
Normal
DClink error
On
Normal
Ovolt m cut
On
Normal
Over voltage
Warning
VL
Safe stop
Warning
SST
Motor PTC
On
Normal
LC Level
Trip/Off/Warn
Via DigIn
Normal/Soft LCL
Содержание F33 Series
Страница 1: ...TECO F33 Variable Speed Drive Instruction manual English Software version 4 2X...
Страница 3: ......
Страница 33: ...30 Getting Started...
Страница 51: ...48 Main Features...
Страница 53: ...50 EMC and Machine Directive...
Страница 59: ...56 Operation via the Control Panel...
Страница 65: ...62 Serial communication...
Страница 159: ...156 Troubleshooting Diagnoses and Maintenance...
Страница 165: ...162 Options...
Страница 179: ...176 Technical Data...
Страница 187: ...184 Menu List...