Functional Description
149
11.8.2 Trip Messages [820] - [890]
Same information as for menu [810].
Communication information
All nine alarm lists contain the same type of data. For
example DeviceNet parameter 31101 in alarm list 1
contains the same data information as 31151 in alarm
list 2. It is possible to read all parameters in alarm lists
2–9 by recalculating the DeviceNet instance number
into a Profibus slot/index number. This is done in the
following way:
slot no = abs((dev instance no-1)/255)
index no = (dev instance no-1) modulo 255
dev instance no = slot index no+1
Example: We want to read out the process value out
from alarm list 9. In alarm list 1 process value has the
DeviceNet instance number 31102. In alarm list 9 it
has DeviceNet instance no 31502 (see table 2 above).
The corresponding slot/index no is then:
slot no = abs((31502-1)/255)=123
index no (modulo)= the remainder of the division above
= 136, calculated as: (31502-1)-123x255=136
11.8.3 Reset Trip Log [8A0]
Resets the content of the 10 trip memories.
Communication information
11.9 System Data [900]
Main menu for viewing all the VSD system data.
11.9.1 VSD Data [920]
VSD Type [921]
Shows the VSD type according to the type number.
The options are indicated on the type plate of the VSD.
Example of type
Communication information
Examples:
JNFX48-046VSD-series suited for 380-480 volt mains
supply, and a rated output current of 46 A.
Software [922]
Shows the software version number of the VSD.
Fig. 120 gives an example of the version number.
Fig. 120 Example of software version
Modbus Instance no/
DeviceNet no:
31151–31185
31201–31235
31251–31285
31301–31335
31351–31385
31401–31435
31451–31485
31501–31535
Trip log list
2
3
4
5
6
7
8
9
Profibus slot/index
122/40–122/74
122/90–122/124
122/140–122/174
122/190–122/224
122/240–123/18
123/35 - 123/68
123/85–123/118
123/135–123/168
Trip log list
2
3
4
5
6
7
8
9
Fieldbus format
Depends on parameter, see respec-
tive parameter.
Modbus format
Depends on parameter, see respec-
tive parameter.
Default:
No
No
0
Yes
1
8A0 Reset Trip
Stp
No
Modbus Instance no/DeviceNet no: 8
Profibus slot/index
0/7
Fieldbus format
UInt
Modbus format
UInt
NOTE: After the reset the setting goes automatically
back to “NO”. The message “OK” is displayed for 2 sec.
NOTE: If the control board is not configured, then type
type shown is JNFX40-XXX.
Modbus Instance no/DeviceNet no: 31037
Profibus slot/index
121/181
Fieldbus format
Long
Modbus format
Text
F33
Stp
JNFX48-046
Stp
V
4.20
Содержание F33 Series
Страница 1: ...TECO F33 Variable Speed Drive Instruction manual English Software version 4 2X...
Страница 3: ......
Страница 33: ...30 Getting Started...
Страница 51: ...48 Main Features...
Страница 53: ...50 EMC and Machine Directive...
Страница 59: ...56 Operation via the Control Panel...
Страница 65: ...62 Serial communication...
Страница 159: ...156 Troubleshooting Diagnoses and Maintenance...
Страница 165: ...162 Options...
Страница 179: ...176 Technical Data...
Страница 187: ...184 Menu List...