13.3.34 #006:illSlotInst
13.3.35 #009:CPU AddrErr
Triggering
Level
Response
An invalid operation code was detected after a
jump command.
Fault
The motor coasts, the microprocessor is stopped and all device
functions are inoperable.
Possible cause
Test
Measure
Acknowledgement
Error in code memory (bit
dumped, permanent).
Reestablish the operating conditions at
the time of the error and check whether
the error occurs again.
•
Reload the application in the
inverter and save it.
•
Perform a firmware upgrade.
Switch device off/on
EMC error
Check the wiring for EMC-compliant
design.
Wire according to EMC regulations.
Triggering
Level
Response
The address for data access is invalid.
Fault
The motor coasts, the microprocessor is stopped and all device
functions are inoperable.
Possible cause
Test
Measure
Acknowledgement
Error in code memory (bit
dumped, permanent).
Reestablish the operating conditions at
the time of the error and check whether
the error occurs again.
•
Reload the application in the
inverter and save it.
•
Perform a firmware upgrade.
Switch device off/on
EMC error
Check the wiring for EMC-compliant
design.
Wire according to EMC regulations.