12.2
Replacing an application
This chapter provides you with a guide to the simple change of an application without extra aids. Only the
Paramodule must be replaced. In the Paramodule, the action
A00 save values
stores the programming and
the parameterization of the inverter safe from a power failure.
The following conditions apply to the replacement:
•
The hardware configuration (option boards, motor settings, etc.) stored on the Paramodule corresponds
to the drive which will use the data of the Paramodule in the future.
•
The programming and parameterization stored on the Paramodule was tested beforehand.
•
After the Paramodule has been exchanged and the drive has been tested, set up the drive again
(referencing, parameter optimization, etc.).
Proceed as shown below:
Replacing the application
1. Start the action
A00 save values
. Wait until the action has been concluded with the result
0:error free
.
2. Turn the power supply of the inverter off. Wait until the indication on the display disappears.
3. Remove the Paramodule from the inverter.
4. Install the new Paramodule (Paramodule with changed application) on the inverter!
5. Connect the power supply.
During startup, the inverter loads the configuration and the new application from the Paramodule and
accepts these.