Diagnosis
Operation
manual
POSIDYN®
SDS
5000
16
2
ID 44
22
8
9
.0
6
WE KEEP THINGS MOVING
13
13.3.13 44:External fault
Triggering
Level
Response
Fault counter
Application-specific or by free
programming option
Fault
The parameterized fault reaction in the
A29
parameter:
•
A29 = 0:inactive
The power unit is switched off, the motor coasts down. The
holding brakes are applied when the purge override is
inactive.
•
A29 = 1:active
The drive is stopped with a quick stop. The holding brakes are
applied at the end of a quick stop if the purge override is
inactive.
Z44
Possible cause
Test
Measure
Acknowledgement
Application-specific or
based on free
programming option;
can be separately
programmed for each
axis
—
—
Switch the device off/on or
programmed
acknowledgement