Adjusting the IP address of the inverter
Follow these steps to adjust the IP address of the inverter to the IP address of the computer:
3. Click one of the two
Determine settings
from network adapter
buttons.
The following dialog screen appears:
4. In the top part of the dialog screen, select the network interface which is connected with the direct
connection to the inverter.
The IP address and the subnet mask of the PC on this interface are indicated in the IP address field.
Adjusting the IP address of the inverter
1. Determine the IP address and subnet mask of the computer, for example from the control panel of your
computer.
2. Determine an IP address that is in the same subnet as the PC's IP address.
3. Use the operator panel of the gateway device to enter that address in parameter
A164[x]
. Use
A164[0]
if
the direct connection is via X3A. Use
A164[1]
if you are connecting the PC via X3B.
4. Check whether either
0:manual
or
1:standard
is entered in
A166[x]
. Note in this case as well that
A166[0]
applies to X3A, while
A166[1]
applies to X3B.
5. If
A166[x]
is not set to
0:manual
or
1:standard
, correct the setting.
6. Save your settings with
A00 Save values
.
You have adjusted the IP address of the inverter.