11.4.10 Deactivation of remote maintenance
NOTICE
Long timeout times on the teleserver!
Do not deactivate remote maintenance by turning the device off and on again because this will result in long
timeout times on the teleserver.
Use one of the following methods to deactivate remote maintenance.
Remote maintenance can be deactivated by the following events:
•
The machine technician switches off the signal (low level) specified in
A167
for all inverters on the IGB
network.
•
The service employee exits remote maintenance in POSITool by pressing the
button when an
Internet connection exists, or the
button for a LAN connection.
•
The Internet connection is interrupted (e.g., by a timeout ). Any specified session ID is always invalid. The
blue LED goes off. To establish a new connection, the procedure in chapter 11.4.8 Activation of remote
maintenance must be performed again.
Note the
A178
parameter when you deactivate remote maintenance. A number value is specified here as to
why the deactivation occurred and whether it was free of errors.
Also remember that after remote maintenance is concluded in POSITool, the signal specified in
A167
must
first be switched to low before remote maintenance can be activated again. Remote maintenance is then
activated again the next time a switch to high is made.
Information
Deactivate remote maintenance immediately after the job is finished. Do not let a request exist for
an unnecessarily long period of time.