Diagnosis
Operation
manual
POSIDYN®
SDS
5000
15
6
ID 44
22
8
9
.0
6
WE KEEP THINGS MOVING
13
13.3.8
38:TempDev.sens
Triggering
Level
Response
Fault counter
The temperature measured by the device sensor
exceeds the permitted maximum value or has
fallen below the permitted minimum value. The
permitted temperatures are saved in the power
unit of the inverter.
Fault
The parameterized fault reaction in the
A29
parameter.
Z38
Possible cause
Test
Measure
Acknowledgement
The ambient/control
cabinet temperatures are
too high or too low.
Correct the surrounding temperature of
the inverter.
Take suitable measures to match the
surrounding temperature to the operating
conditions of the inverter.
Switch the device off/on or
programmed
acknowledgement
Fan faulty
Switch on the control unit power supply
and check whether the fan(s) start up.
Replace the inverter.