Technician
Operations
108
RB6741-Z Touchscreen Security System Installation Manual
The Cross Zone Associations screen
appears.
2.
Touch
Add
. The Add Cross-Zone
Associations screen appears.
3.
Touch a sensor/security zone listed in the
First Zone
column.
4.
Touch a different sensor/security listed in the
Second Zone
column.
5.
In the
Cross Zone Timeout
field, touch the arrows to set the number of seconds that the
system will wait after one of the sensors is faulted to see whether the other sensor is
faulted.
6.
Touch
Save
to create the cross-zone association.