2.1 General
46
SIPROTEC 4, 7SJ62/63/64 Handbuch
C53000-G1140-C147-A, Edition 07.2015
Distance Unit
Address
215
Distance Unit
corresponds to the unit of length (
km
or
Miles
) appli-
cable to fault locating. If a fault locator is not included with the device, or if the fault
locating function is disabled, this setting has no effect on operation of the device.
Changing the length unit will not result in an automatic conversion between the sys-
tems. Such conversions must be entered at the appropriate addresses.
ATEX100
Address
235
ATEX100
allows that the requirements for the protection of explosion-
protected motors with regard to thermal profiles is fulfilled. Set this parameter to
YES
to save all thermal replicas of devices 7SJ62/63/64 in the event of a power supply fail-
ure. After the supply voltage is restored the thermal profiles will resume operation
using the stored values. Set the parameter to
NO
to reset the calculated overtempera-
tures of all thermal profiles to zero if the power supply fails.
Two-phase Time
Overcurrent Pro-
tection (Power
System Data)
Two-phase time overcurrent protection is used in isolated or resonant-grounded
systems where three-phase devices are desired to coact with existing two-phase pro-
tection equipment. Parameter
250
50/51 2-ph prot
can be set to specify whether
the overcurrent protection operates in two or three phases. If set to
ON
, threshold com-
parison uses always the value 0A instead of the measured value for
I
B
, so that phase
B can not initiate a pick-up. All other functions operate however in three phases.
Ground Fault Pro-
tection
With address
613
Gnd O/Cprot. w.
define whether ground fault protection either
is to operate using measured values (
Ignd (measured)
) or the quantities calculated
from the three phase currents (
3I0 (calcul.)
). In the first case, the measured
quantity at the fourth current input is evaluated. In the latter case, the summation
current is calculated from the three phase current inputs. If the device features a sen-
sitive ground current input (measuring range starts at 1 mA), the ground fault protec-
tion always uses the calculated quantity 3I0. In this case, parameter
613
Gnd
O/Cprot. w.
is not available.
Voltage Protection
(Switchover of
Characteristic
Values)
With three-phase connection, the fundamental harmonic component of the largest of
the three phase-to-phase voltages (
Vphph
) is supplied to the overvoltage protection
elements, or the negative sequence voltage (
V2
). With three-phase connection, und-
ervoltage protection relies either on the positive sequence voltage
V1
or the smallest
of the phase-to-phase voltages
Vphph
. These specifications can be configured via pa-
rameter
614
OP. QUANTITY 59
and
615
OP. QUANTITY 27
. If voltage transform-
ers are connected single-phase, there is a direct comparison of measured values and
thresholds, and the setting of characteristic values switchover is ignored.
Nominal Values of
Current Transform-
ers (CTs)
At addresses
204
CT PRIMARY
and
205
CT SECONDARY
, information is entered re-
garding the primary and secondary ampere ratings of the current transformers. It is im-
portant to ensure that the rated secondary current of the current transformers matches
the rated current of the device, otherwise the device will incorrectly calculate primary
data. At addresses
217
Ignd-CT PRIM
and
218
Ignd-CT SEC
, information is
entered regarding the primary and secondary ampere rating of the current transform-
ers. In case of normal connection (starpoint current connected to
I
N
–transformer)
217
Ignd-CT PRIM
and
204
CT PRIMARY
must be set to the same value.
If the device features a sensitive ground current input, address
218
Ignd-CT SEC
is
set to 1 A. In this case setting cannot be changed.
Nominal Values of
Voltage Transform-
ers (VTs)
At addresses
202
Vnom PRIMARY
and
203
Vnom SECONDARY
, information is entered
regarding the primary nominal voltage and secondary nominal voltage (phase-to-
phase) of the connected voltage transformers.
Содержание siprotec SJ62
Страница 3: ...3 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Страница 9: ...Preface 9 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Страница 21: ...Contents 19 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Страница 35: ...1 Introduction 33 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Страница 365: ...2 Functions 363 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Страница 443: ...3 Mounting and Commissioning 441 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Страница 529: ...4 Technical Data 527 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Страница 699: ...A Appendix 697 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Страница 701: ...Literature 699 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Страница 714: ...Index 712 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Страница 715: ...Index 713 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...