2.6 Voltage Protection 27, 59
144
SIPROTEC 4, 7SJ62/63/64 Handbuch
C53000-G1140-C147-A, Edition 07.2015
this feature prevents an immediate general pickup of the device when the device is
powered-up without measurement voltage being present.
Note
If parameter
CURRENT SUPERV.
is set to disabled in address
5120
, the device picks
up without measurement voltage and the undervoltage protection function in pickup.
Further configuration can be performed by pickup of measurement voltage or blocking
voltage protection. The latter can be initiated via device operation in DIGSI and via
communication from the control centre by means of a tagging command for blocking
voltage protection. This causes the dropout of the pickup and parameterization can be
resumed.
Please note that pickup threshold
BkrClosed I MIN
is used in other protective func-
tions as well, including breaker failure protection, overload protection, and start inhibit
for motors.
2.6.5
Settings
Addresses which have an appended "A" can only be changed with DIGSI, under "Dis-
play Additional Settings".
Addr.
Parameter
Setting Options
Default Setting
Comments
5001
FCT 59
OFF
ON
Alarm Only
OFF
59 Overvoltage Protection
5002
59-1 PICKUP
40 .. 260 V
110 V
59-1 Pickup
5003
59-1 PICKUP
40 .. 150 V
110 V
59-1 Pickup
5004
59-1 DELAY
0.00 .. 100.00 sec;
∞
0.50 sec
59-1 Time Delay
5005
59-2 PICKUP
40 .. 260 V
120 V
59-2 Pickup
5006
59-2 PICKUP
40 .. 150 V
120 V
59-2 Pickup
5007
59-2 DELAY
0.00 .. 100.00 sec;
∞
0.50 sec
59-2 Time Delay
5015
59-1 PICKUP V2
2 .. 150 V
30 V
59-1 Pickup V2
5016
59-2 PICKUP V2
2 .. 150 V
50 V
59-2 Pickup V2
5017A
59-1 DOUT RATIO
0.90 .. 0.99
0.95
59-1 Dropout Ratio
5018A
59-2 DOUT RATIO
0.90 .. 0.99
0.95
59-2 Dropout Ratio
5101
FCT 27
OFF
ON
Alarm Only
OFF
27 Undervoltage Protection
5102
27-1 PICKUP
10 .. 210 V
75 V
27-1 Pickup
5103
27-1 PICKUP
10 .. 120 V
75 V
27-1 Pickup
5106
27-1 DELAY
0.00 .. 100.00 sec;
∞
1.50 sec
27-1 Time Delay
5110
27-2 PICKUP
10 .. 210 V
70 V
27-2 Pickup
5111
27-2 PICKUP
10 .. 120 V
70 V
27-2 Pickup
5112
27-2 DELAY
0.00 .. 100.00 sec;
∞
0.50 sec
27-2 Time Delay
Содержание siprotec SJ62
Страница 3: ...3 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Страница 9: ...Preface 9 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Страница 21: ...Contents 19 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Страница 35: ...1 Introduction 33 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Страница 365: ...2 Functions 363 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Страница 443: ...3 Mounting and Commissioning 441 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Страница 529: ...4 Technical Data 527 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Страница 699: ...A Appendix 697 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Страница 701: ...Literature 699 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Страница 714: ...Index 712 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Страница 715: ...Index 713 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...