2 Functions
267
SIPROTEC 4, 7SJ62/63/64 Handbuch
C53000-G1140-C147-A, Edition 07.2015
2.17.2 Setting Notes
The Device Configuration allows the user to specify the number of flexible protection
functions to be used (see also chapter 2.1.1). If a flexible function is disabled in the
Device Configuration (removing the checkmark), all settings and configurations asso-
ciated with this function are deleted or reset to their default values.
General
The „General“ dialog box in DIGSI offers parameter
FLEXIBLE FUNC.
which can be
set to
OFF
,
ON
or
Alarm Only
. In
Alarm Only
mode, the function does not open
fault logs, initiate „Active“ indications or trip commands and nor does it influence the
breaker failure protection. This operating mode is therefore preferable if a flexible
function is not desired to work as protective function. Besides that the
OPERRAT.
MODE
can be configured:
3-phase
– The functions evaluate the three-phase measuring system, i.e. all three
phases are covered in parallel. A typical example is the three-phase time overcurrent
protection.
1-phase
– The functions evaluate only the individual measured value. This may be an
individual phase value (e.g. V
B
) or a ground quantity (V
N
or
I
N
).
If set to
no reference
, the measured values are evaluated irrespective of whether
current and voltage are connected in one or three phases. Table 2.17 provides an
overview of which characteristics can be operated in which mode.
Measured Quantity
In the „Measured quantity“ dialog box, the user can select the measured value the pro-
tective function evaluates. This value may be calculated or measured directly. The
offered setting options depend on the type of measured value processing in parameter
OPERRAT. MODE
(see following table).
Table 2-19
Parameters “Operating Mode” and “Measured Quantity”
Measurement
Method
The measurement methods listed in the following tables can be set for the measured
quantities of current, voltage and power. They also indicate how the available mea-
surement method, depend on the selected operating mode and the measured quanti-
ty.
Parameter
OPERRAT. MODE
Setting
Parameter
MEAS. QUANTITY
Setting option
1-phase,
3-phase
Current
Voltage
P forward
P reverse
Q forward
Q reverse
Power factor
without reference
Frequency
df/dt rising
df/dt falling
Binray Input
Содержание siprotec SJ62
Страница 3: ...3 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Страница 9: ...Preface 9 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Страница 21: ...Contents 19 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Страница 35: ...1 Introduction 33 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Страница 365: ...2 Functions 363 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Страница 443: ...3 Mounting and Commissioning 441 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Страница 529: ...4 Technical Data 527 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Страница 699: ...A Appendix 697 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Страница 701: ...Literature 699 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Страница 714: ...Index 712 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Страница 715: ...Index 713 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...