2.12 Ground Fault Protection 64, 67N(s), 50N(s), 51N(s)
212
SIPROTEC 4, 7SJ62/63/64 Handbuch
C53000-G1140-C147-A, Edition 07.2015
The following must be observed:
• The value pairs should be entered in increasing sequence. Fewer than 20 pairs is
also sufficient. In most cases, about 10 pairs is sufficient to define the characteristic
accurately. A value pair which will not be used has to be made invalid by entering
"
∞
” for the threshold! The user must ensure the value pairs produce a clear and con-
stant characteristic.
The current values entered should be those from Table 2-3, along with the matching
times. Deviating values MofPU (multiples of PU-values) are rounded. This, howev-
er, will not be indicated.
Currents less than the smallest current value entered will not lead to an extension
of the tripping time. The pickup curve (see Figure 2-77) continues, from the smallest
current point parallel to the current axis.
Currents greater than the highest current value entered will not lead to a reduction
of the tripping time. The pickup curve (see Figure 2-77) continues, from the largest
current point parallel to the current axis.
Table 2-12
Preferential values of standardized currents for user-defined tripping curves
Figure 2-77
Use of a user-defined characteristic
Determination of
Ground-Faulted
Phase
The ground-faulted phase may be identified in an ungrounded or resonant-grounded
system, if the device is supplied by three voltage transformers connected in a ground-
ed-wye configuration. The phase in which the voltage lies below setting
VPH MIN
at
address
3106
is identified as the faulty phase as long as the other two phase voltages
simultaneously exceed the setting
VPH MAX
at address
3107
. The setting
VPH MIN
must be set less than the minimum expected operational phase-to-ground voltage. A
typical setting for this address would be 40 V. Setting
VPH MAX
must be greater than
MofPU = 1 to 1.94
MofPU = 2 to 4.75
MofPU = 5 to 7.75
MofPU = 8 to 20
1.00
1.50
2.00
3.50
5.00
6.50
8.00
15.00
1.06
1.56
2.25
3.75
5.25
6.75
9.00
16.00
1.13
1.63
2.50
4.00
5.50
7.00
10.00
17.00
1.19
1.69
2.75
4.25
5.75
7.25
11.00
18.00
1.25
1.75
3.00
4.50
6.00
7.50
12.00
19.00
1.31
1.81
3.25
4.75
6.25
7.75
13.00
20.00
1.38
1.88
14.00
1.44
1.94
Содержание siprotec SJ62
Страница 3: ...3 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Страница 9: ...Preface 9 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Страница 21: ...Contents 19 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Страница 35: ...1 Introduction 33 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Страница 365: ...2 Functions 363 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Страница 443: ...3 Mounting and Commissioning 441 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Страница 529: ...4 Technical Data 527 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Страница 699: ...A Appendix 697 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Страница 701: ...Literature 699 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Страница 714: ...Index 712 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Страница 715: ...Index 713 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...