2 Functions
201
SIPROTEC 4, 7SJ62/63/64 Handbuch
C53000-G1140-C147-A, Edition 07.2015
Determination of
the Grounded
Phase
After the voltage element picks up due to detection of a displacement voltage, the
grounded phase is identified, if possible. To do this, the individual phase-to-ground
voltages are measured. Of course, this is only possible if three phase-to-ground volt-
ages are obtained from voltage transformers connected in a grounded-wye configura-
tion. If the voltage magnitude for any given phase is below the setting value V
Ph min
that
phase is detected as the grounded phase as long as the remaining phase-ground volt-
ages are simultaneously above the setting value V
Ph max
.
The following figure shows the logic for determining the grounded phase.
Figure 2-67
Determination of Grounded Phase
2.12.2 Current Elements 50Ns, 51Ns
The current elements for ground faults operate with the magnitudes of the ground cur-
rent. They only make sense where the magnitude of the ground current can be used
to specify the ground fault. This may be the case on grounded systems (solid or low-
resistance) or on electrical machines which are directly connected to the busbar of an
isolated power system, when in case of a network ground fault the machine supplies
only a negligible ground fault current across the measurement location, which must be
situated between the machine terminals and the network, whereas in case of a
machine ground fault the higher ground fault current produced by the total network is
available. Ground current protection is mostly used as backup protection for high re-
sistance ground faults in solid or low resistance grounded systems when main fault
protection does not pickup.
For ground fault detection, a two-step current/time characteristic can be set. Analog to
the time overcurrent protection, the high-set current element is designated as
50Ns-
2 PICKUP
and
50Ns-2 DELAY
and is provided with a definite time characteristic.
The overcurrent element may be operated with either a definite time delay (
50Ns-1
PICKUP
and
50Ns-1 DELAY
) or with a user-defined characteristic (
51Ns PICKUP
Содержание siprotec SJ62
Страница 3: ...3 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Страница 9: ...Preface 9 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Страница 21: ...Contents 19 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Страница 35: ...1 Introduction 33 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Страница 365: ...2 Functions 363 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Страница 443: ...3 Mounting and Commissioning 441 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Страница 529: ...4 Technical Data 527 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Страница 699: ...A Appendix 697 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Страница 701: ...Literature 699 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Страница 714: ...Index 712 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Страница 715: ...Index 713 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...