2.1 General
44
SIPROTEC 4, 7SJ62/63/64 Handbuch
C53000-G1140-C147-A, Edition 07.2015
2.1.3
Power System Data 1
2.1.3.1
Description
The device requires certain basic data regarding the protected equipment, so that the
device can adapt to its desired application. These may be, for instance, nominal power
system and transformer data, measured quantity polarities and their physical connec-
tions, breaker properties (where applicable) etc. There are also certain parameters
that are common to all functions, i.e. not associated with a specific protection, control
or monitoring function. The following section discusses these data.
2.1.3.2
Setting Notes
General
This data can be entered directly on the device featuring an integrated or detached
operator panel for parameters
209
PHASE SEQ.
,
210
TMin TRIP CMD
,
211
TMax
CLOSE CMD
and
212
BkrClosed I MIN
. Select the MAIN MENU by pressing the
MENU
key. Press the
▼
key to select
SETTINGS
and the
X
key to navigate to the set-
tings selection. To obtain the Power System Data display, select the
P.System Data
1
in the
SETTINGS
menu.
In DIGSI double-click on
Settings
to display the relevant selection. A dialog box will
open under the option
P.System Data 1
with the tabs Power system, CTs, VTs and
Breaker where you can configure the individual parameters. Thus the following Sub-
sections are structured accordingly.
Nominal Frequency
The rated system frequency is set at address
214
Rated Frequency
. The factory
presetting in accordance with the model number must only be changed if the device
will be employed for a purpose other than that which was planned when ordering.
Phase Rotation Re-
versal
Address
209
PHASE SEQ.
is used to change the default phase sequence (
A B C
for
clockwise rotation), if your power system permanently has an anti-clockwise phase se-
quence (
A C B
). A temporary reversal of rotation is also possible using binary inputs
(see Section 2.21.2).
Temperature Unit
Address
276
TEMP. UNIT
allows you to display the temperature values either in
degree Celsius or in degree Fahrenheit.
Polarity of Current
Transformers
At address
201
CT Starpoint
, the polarity of the wye-connected current transform-
ers is specified (the following figure applies correspondingly for two current transform-
ers). This setting determines the measuring direction of the device (forwards = line di-
rection). Modifying this setting also results in a polarity reversal of the ground current
inputs
I
N
or
I
NS
.
Содержание siprotec SJ62
Страница 3: ...3 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Страница 9: ...Preface 9 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Страница 21: ...Contents 19 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Страница 35: ...1 Introduction 33 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Страница 365: ...2 Functions 363 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Страница 443: ...3 Mounting and Commissioning 441 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Страница 529: ...4 Technical Data 527 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Страница 699: ...A Appendix 697 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Страница 701: ...Literature 699 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Страница 714: ...Index 712 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Страница 715: ...Index 713 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...