2 Functions
143
SIPROTEC 4, 7SJ62/63/64 Handbuch
C53000-G1140-C147-A, Edition 07.2015
The time delay settings should be set that tripping results when voltage dips occur,
which could lead to unstable operating conditions. On the other hand, the time delay
should be long enough to avoid tripping due to momentary voltage dips.
Undervoltage protection includes two definite time elements. The pickup value of the
lower threshold is set at address
5110
or
5111
,
27-2 PICKUP
(depending on the
voltage transformer connection, phase-to-ground or phase-to-phase), while time
delay is set at address
5112
,
27-2 DELAY
(short time delay). The pickup value of the
upper element is set at address
5102
or
5103
,
27-1 PICKUP
, while the time delay
is set at address
5106
,
27-1 DELAY
(a somewhat longer time delay). Setting these
elements in this matter allows the undervoltage protection function to closely follow the
stability behaviour of the system.
Undervoltage Pro-
tection with Phase
Voltages
The smallest of the phase-to-phase voltages
Vphph
can also be configured as mea-
sured quantity for the undervoltage protection with three-phase connection by means
of parameter
615
OP. QUANTITY 27
instead of the positive sequence component
(
V1
). The threshold values have to be set as phase-phase quantities.
The time delay settings should be set that tripping results when voltage dips occur
which could lead to unstable operating conditions. On the other hand, the time delay
should be long enough to permissable short voltage dips.
Undervoltage protection includes two definite time elements. The pickup value of the
lower threshold is set at address
5110
or
5111
,
27-2 PICKUP
(depending on the
voltage transformer connection, phase-to-ground or phase-to-phase), while time
delay is set at address
5112
,
27-2 DELAY
(short time delay). The pickup value of the
upper element is set at address
5102
or
5103
,
27-1 PICKUP
, while the time delay
is set at address
5106
,
27-1 DELAY
(a somewhat longer time delay). Setting these
elements in this matter allows the undervoltage protection function to closely follow the
stability behaviour of the system.
Dropout Threshold
of the Undervoltage
Protection
The dropout thresholds of the
27-1
element and the
27-2
element can be set via the
dropout ratio r = V
dropout
/V
pickup
(
5113
27–1 DOUT RATIO
or
5114
27–2 DOUT
RATIO
). In this, the following marginal condition always holds for r:
r · (configured pickup threshold )
≤
120 V with connection of phase-to-phase voltages
or
r · (configured pickup threshold )
≤
210 V with connection of phase-to-ground voltages.
The minimum hysteresis is 0.6 V.
Note
If a setting is selected such that the dropout threshold (= pickup threshold · dropout
ratio) results in a greater value than 120 V / 210 V, it will be limited automatically. No
error message occurs.
Current Criterion
for Undervoltage
Protection
The 27-2 and 27-1 elements can be supervised by the current flow monitoring setting.
If the
CURRENT SUPERV.
is switched ON at address
5120
(factory setting), the
release condition of the current criterion must be fulfilled in addition to the correspond-
ing undervoltage condition, which means that a configured minimum current
(
BkrClosed I MIN
, address
212
) must be present to make sure that this protective
function can pick up. Therefore, it is possible to achieve that pickup of undervoltage
protection drops out when the line is disconnected from voltage supply. Furthermore,
Содержание siprotec SJ62
Страница 3: ...3 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Страница 9: ...Preface 9 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Страница 21: ...Contents 19 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Страница 35: ...1 Introduction 33 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Страница 365: ...2 Functions 363 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Страница 443: ...3 Mounting and Commissioning 441 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Страница 529: ...4 Technical Data 527 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Страница 699: ...A Appendix 697 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Страница 701: ...Literature 699 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Страница 714: ...Index 712 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Страница 715: ...Index 713 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...