2 Functions
209
SIPROTEC 4, 7SJ62/63/64 Handbuch
C53000-G1140-C147-A, Edition 07.2015
Figure 2-74
Determination of the ground fault location basing on directional indicators in the
meshed system
2.12.6 Setting Notes
General Settings
The operating mode of the protective function is configured at address
131
Sens.
Gnd Fault
(see Section 2.1.1). If address
Sens. Gnd Fault
=
Definite Time
,
then only the settings for the definite-time elements are available. If the setting is
Sens. Gnd Fault
=
Log. inverse A
, a logarithmic inverse characteristic is avail-
able. If the setting is
Sens. Gnd Fault
=
Log. Inverse B
, a logarithmic inverse
characteristic with knee point is active. Alternatively, user-defined characteristic can
be used when setting
Sens. Gnd Fault
=
User Defined PU
. The superimposed
high-set element 50Ns-2 is available in all these cases. If the function is not required,
Disabled
is set.
Address
213
VT Connect. 3ph
specifies how the voltage transformers are connect-
ed (phase-ground or phase-phase). Furthermore, adaption factor
Vph / Vdelta
for
displacement voltage are properly set in address
206
, primary and secondary nominal
transformer current in the ground path are properly set in addresses
217
and
218
.
Sensitive ground fault detection may be switched
ON
or
OFF
or to
Alarm Only
in
address
3101
Sens. Gnd Fault
. If sensitive ground fault protection is switched
ON
,
both tripping and message reporting is possible.
The ground fault is detected and reported only when the displacement voltage was
present for at least the time
T-DELAY Pickup
(address
3111
).
Address
3130
PU CRITERIA
specifies whether ground fault detection is enabled only
for pickups of V
0
and
I
Ns
(
Vgnd AND INs
) or as soon as one of the two has picked
up (
Vgnd OR INs
).
A two-stage current/time characteristic may be set at addresses
3113
through
3120
.
Each of these elements may be directional or non-directional. These elements operate
with the ground current magnitude. They only make sense where the magnitude of the
ground current and maybe the direction can be used to specify the ground fault. This
may be the case on grounded systems (solid or low-resistant) or on electrical ma-
chines which are directly connected to the busbar of an ungrounded power system,
when in case of a network ground fault the machine supplies only a negligible ground
fault current across the measurement location, which must be situated between the
machine terminals and the network, whereas in case of a machine ground fault the
total ground fault current produced by the total network is available.
Содержание siprotec SJ62
Страница 3: ...3 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Страница 9: ...Preface 9 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Страница 21: ...Contents 19 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Страница 35: ...1 Introduction 33 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Страница 365: ...2 Functions 363 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Страница 443: ...3 Mounting and Commissioning 441 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Страница 529: ...4 Technical Data 527 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Страница 699: ...A Appendix 697 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Страница 701: ...Literature 699 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Страница 714: ...Index 712 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Страница 715: ...Index 713 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...