2.5 Single-Phase Overcurrent Protection
132
SIPROTEC 4, 7SJ62/63/64 Handbuch
C53000-G1140-C147-A, Edition 07.2015
If performance makes it necessary to switch several varistors in parallel, preference
should by given to types with a flat characteristic to avoid asymmetrical loading. We
therefore recommend the following types from METRSIL:
600A/S1/S256 (k = 450,
β
= 0.25)
600A/S1/S1088 (k = 900,
β
= 0.25)
The pickup value (0.1 A or 0.05 A in the example) is set in address
2706
50 1Ph-1
PICKUP
in the device. The
50-2
element is not required (address
2703
50 1Ph-2
PICKUP
=
∞
).
The trip command of the element can be delayed in address
2707
50 1Ph-1 DELAY
.
This delay is normally set to 0.
If a higher number of CT's is connected in parallel, e.g. as busbar protection with
several feeders, the magnetizing currents of the transformers connected in parallel
cannot be neglected any more. In this case, the magnetizing currents at the half knee-
point voltage (corresponds to the setting value) have to be summed up. These mag-
netizing currents reduce the current through the resistor R. Therefore the actual
pickup value will be correspondingly higher.
Use as Tank
Leakage Protection
The use as tank leakage protection requires that a sensitive input transformer is avail-
able at the device input
I
N
/
I
NS
. In this case, only the pickup value for single phase over-
current protection is set at the 7SJ62/63/64 device for the current at input
I
N
/
I
NS
.
The tank leakage protection is a sensitive overcurrent protection which detects the
leakage current between the isolated transformer tank and ground. Its sensitivity is set
in address
2706
50 1Ph-1 PICKUP
. The
50-2
element is not required (address
2703
50 1Ph-2 PICKUP
=
∞
).
The trip command of the element can be delayed in address
2707
50 1Ph-1 DELAY
.
It is normally set to
0
.
Note
In the following Setting overview addresses
2703
and
2706
are valid for a highly sen-
sitive current measuring input independently of the nominal current.
Содержание siprotec SJ62
Страница 3: ...3 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Страница 9: ...Preface 9 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Страница 21: ...Contents 19 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Страница 35: ...1 Introduction 33 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Страница 365: ...2 Functions 363 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Страница 443: ...3 Mounting and Commissioning 441 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Страница 529: ...4 Technical Data 527 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Страница 699: ...A Appendix 697 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Страница 701: ...Literature 699 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Страница 714: ...Index 712 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Страница 715: ...Index 713 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...