2 Functions
289
SIPROTEC 4, 7SJ62/63/64 Handbuch
C53000-G1140-C147-A, Edition 07.2015
The associated messages indicating the release via the corresponding condition are
as follows:
„25 V1> V2<“
,
„25 V1< V2>“
and
„25 V1< V2<“
.
Via binary input
„>25 V1>V2<“
,
„>25 V1<V2>“
and
„>25 V1<V2<“
release con-
ditions can be issued externally provided the synchrocheck is controlled externally.
Parameter
TSUP VOLTAGE
(address
6111
) can be set to configure a monitoring time
which requires above stated release conditions for de-energized connection to be ful-
filled at least this time before switching is allowed.
2.19.1.5 Direct Command / Blocking
Parameter
Direct CO
can be set to grant a release without performing any checks.
In this case switching is released immediately when initiating the synchrocheck. It is
obviously not reasonable to combine
Direct CO
with other release conditions.
If the synchrocheck fails, depending on the type of failure a direct command bypassing
any checks may be issued or not (also see "Plausibility check / SYNC Error").
Via binary input
„>25direct CO“
this release can also be granted externally.
Blocking the entire synchrocheck is possible via binary input
„>BLK 25-1“
. The
message signaling this condition is made via
„25-1 BLOCK“
. When blocking the
measurement is terminated and the entire function is reset. A new measurement can
only be performed with a new measurement request.
Via binary input
„>BLK 25 CLOSE“
it is possible to only block the release signal for
closing (
„25 CloseRelease“
). When blocking is active, measurement continues.
The blocking is indicated by the message
„25 CLOSE BLK“
. When blocking is reset
and release conditions are fulfilled, the release signal for closing is issued.
2.19.1.6 SYNC Function Groups
The 7SJ64 relay comprises 4 SYNC function groups (SYNC function group 1 to 4)
whereby each group contains all setting parameters required by a SYNC function. This
generally includes the switchgear component for which the SYNC function settings are
to be applied.
However, several SYNC function groups may be used for one point of synchroniza-
tion/switching object if synchronismn is to be performed with different parameters. Al-
location of switchgear component and SYNC function group must then be accom-
plished dynamically (whichever is the function group to operate with) via one of the
binary inputs from
„>25-1 act“
to
„>25-4 act“
.
If the assignment to the SYNC groups is clear, the binary inputs are not required.
Selecting one SYNC function group several times, causes output of error message
(
„25 FG-Error“
).
Содержание siprotec SJ62
Страница 3: ...3 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Страница 9: ...Preface 9 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Страница 21: ...Contents 19 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Страница 35: ...1 Introduction 33 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Страница 365: ...2 Functions 363 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Страница 443: ...3 Mounting and Commissioning 441 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Страница 529: ...4 Technical Data 527 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Страница 699: ...A Appendix 697 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Страница 701: ...Literature 699 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Страница 714: ...Index 712 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Страница 715: ...Index 713 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...