4 Technical Data
451
SIPROTEC 4, 7SJ62/63/64 Handbuch
C53000-G1140-C147-A, Edition 07.2015
System Interface
IEC 60870-5-103
RS232/RS485/FO accord-
ing to the ordering variant
isolated interface for data transfer to a
master terminal
RS232
Connection for flush-
mounted case
Rear panel, mounting location „B“, 9-
pin D-SUB miniature connector
Connection for surface
mounting housing
at the housing mounted case on the
case bottom
Test Voltage
500 VAC
Transmission Speed
min. 4,800 Baud; max. 38,400 Baud;
Factory setting 9600 Baud
Maximum Distance of
Transmission
49.2 feet (15 m)
RS485
Connection for flush-
mounted case
Rear panel, mounting location „B“, 9-
pin D-SUB miniature connector
Connection for surface
mounting housing
at the housing mounted case on the
case bottom
Test Voltage
500 VAC
Transmission Speed
min. 4,800 Baud; max. 38,400 Baud;
Factory setting 9600 Baud
Maximum Distance of
Transmission
max. 0.62 miles (1 km)
Fiber Optical Link (FO)
FO connector type
ST connector
Connection for flush-
mounted case
Rear panel, mounting location „B“
Connection for surface
mounting housing
at the housing mounted case on the
case bottom
Optical Wavelength
λ
= 820 nm
Laser Class 1 according to
EN 60825-1/-2
using glass fiber 50/12
μ
m or using
glass fiber 62.5/125
μ
m
Permissible Optical Link
Signal Attenuation
max. 8 dB, with glass fiber 62.5/125
μ
m
Maximum Distance of
Transmission
max. 0.93 miles (1.5 km)
Character Idle State
Configurable: factory setting „Light off“
PROFIBUS RS485
(FMS and DP)
Connection for flush-
mounted case
Rear panel, mounting location „B“ 9-
pin D-SUB miniature connector
Connection for surface
mounting housing
at the housing mounted case on the
case bottom
Test Voltage
500 VAC
Transmission Speed
up to 1.5 MBd
Maximum Distance of
Transmission
3,280 ft or 1,000 m at
≤
93.75 kBd
500 m or 1,640 ft at
≤
187.5 kBd
200 m or 330 ft at
≤
1.5 MBd
Содержание siprotec SJ62
Страница 3: ...3 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Страница 9: ...Preface 9 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Страница 21: ...Contents 19 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Страница 35: ...1 Introduction 33 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Страница 365: ...2 Functions 363 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Страница 443: ...3 Mounting and Commissioning 441 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Страница 529: ...4 Technical Data 527 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Страница 699: ...A Appendix 697 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Страница 701: ...Literature 699 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Страница 714: ...Index 712 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Страница 715: ...Index 713 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...