2.23 Auxiliary Functions
330
SIPROTEC 4, 7SJ62/63/64 Handbuch
C53000-G1140-C147-A, Edition 07.2015
The summated values can be interpreted as the number of tripping operations at rated
operational current of the CB. They are displayed in the statistics values without unit
and with two decimal places.
2P-Procedure
Parameter
172
52 B.WEAR MONIT
can be set to activate the 2P-procedure. An op-
erating cycles diagram (see sample diagram in the functional description of the 2P-
procedure), provided by the manufacturer, shows the relationship of make-break op-
erations and tripping current. The two vertices of this characteristic in a double-loga-
rithmic scale are decisive for the setting of address
260
to
263
:
Point P1 is determined by the number of permitted make-break operations (parameter
261
OP.CYCLES AT Ir
) for rated operational current
I
r (parameter
260
Ir-52
)
Point P2 is determined by the maximum number of make-break operations (parameter
263
OP.CYCLES Isc
) for rated fault tripping current
I
sc (parameter
262
Isc-52
).
For the procedure to operate correctly, the time response of the circuit breaker must
be specified in parameters
266
T 52 BREAKTIME
and
267
T 52 OPENING
.
I
2
t-Procedure
Parameter
172
52 B.WEAR MONIT
is set to activate the
I
2
t-procedure (only 7SJ64).
The squared tripping currrent integrals are referred to the squared nominal current of
the device. In order to calculate the arcing time, the device requires the CB tripping
time
T 52 BREAKTIME
and the CB operating time
T 52 OPENING
. The „current zero“
criterion is required to recognize the last zero crossing (arc extinction) of the currents
after a trip.
2.23.3.4 Information List
No.
Information
Type of In-
formation
Comments
-
#of TRIPs=
PMV
Number of TRIPs=
409
>BLOCK Op Count
SP
>BLOCK Op Counter
1020
Op.Hours=
VI
Counter of operating hours
1021
Σ
Ia =
VI
Accumulation of interrupted current Ph A
1022
Σ
Ib =
VI
Accumulation of interrupted current Ph B
1023
Σ
Ic =
VI
Accumulation of interrupted current Ph C
2896
79 #Close1./3p=
VI
No. of 1st AR-cycle CLOSE commands,3pole
2898
79 #Close2./3p=
VI
No. of higher AR-cycle CLOSE commands,3p
16001
Σ
I^x A=
VI
Sum Current Exponentiation Ph A to Ir^x
16002
Σ
I^x B=
VI
Sum Current Exponentiation Ph B to Ir^x
16003
Σ
I^x C=
VI
Sum Current Exponentiation Ph C to Ir^x
16006
Resid.Endu. A=
VI
Residual Endurance Phase A
16007
Resid.Endu. B=
VI
Residual Endurance Phase B
16008
Resid.Endu. C=
VI
Residual Endurance Phase C
16011
mechan.TRIP A=
VI
Number of mechanical Trips Phase A
16012
mechan.TRIP B=
VI
Number of mechanical Trips Phase B
16013
mechan.TRIP C=
VI
Number of mechanical Trips Phase C
16014
Σ
I^2t A=
VI
Sum Squared Current Integral Phase A
16015
Σ
I^2t B=
VI
Sum Squared Current Integral Phase B
16016
Σ
I^2t C=
VI
Sum Squared Current Integral Phase C
Содержание siprotec SJ62
Страница 3: ...3 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Страница 9: ...Preface 9 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Страница 21: ...Contents 19 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Страница 35: ...1 Introduction 33 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Страница 365: ...2 Functions 363 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Страница 443: ...3 Mounting and Commissioning 441 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Страница 529: ...4 Technical Data 527 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Страница 699: ...A Appendix 697 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Страница 701: ...Literature 699 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Страница 714: ...Index 712 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Страница 715: ...Index 713 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...