2.11 Monitoring Functions
190
SIPROTEC 4, 7SJ62/63/64 Handbuch
C53000-G1140-C147-A, Edition 07.2015
The FFM will pick up on a ground voltage V
N
which is bigger than the threshold spec-
ified under
5302
FUSE FAIL 3Vo
and on a ground current
I
N which is smaller than
the threshold specified under
5303
FUSE FAIL RESID
.
Pickup will take place on the specified values. A hysteresis is integrated for dropout,
of 105% where
I
N
or of 95% where V
N
. In case of a low-current asymmetrical fault in
the power system with weak infeed, the ground current caused by the fault might lie
below the pickup threshold of the Fuse Failure Monitor. Overfunctioning of the Fuse
Failure Monitor can, however, cause the feeder protection equipment to fail since it will
block all protective functions that use voltage signals. Such an overfunction of the FFM
is avoided by additionally checking the phase currents. If at least one phase currents
lies above the pickup threshold of
5303
FUSE FAIL RESID
, it can be assumed that
the zero current created by a short-circuit would equally exceed this limit.
The following conditions hold to immediately detect a fault existing after activation of
the FFM: If a ground current
I
N
occurs within 10 seconds after the Fuse-Failure crite-
rion was detected, a fault is assumed and the blocking by the Fuse Failure Monitor is
blocked for as long as the fault persists. If the voltage failure criterion applies for longer
than approx. 10 seconds, the blocking takes permanent effect. After the time has
elapsed it can be assumed that a Fuse Failure has actually occurred. The blocking is
lifted automatically 10 seconds after the voltage criterion has disappeared as a result
of the secondary circuit fault being cleared, and the entire protection function is re-
leased.
The following figure shows the logic diagram of the Fuse Failure Monitor.
Figure 2-61
Logic diagram of the Fuse Failure Monitor
Содержание siprotec SJ62
Страница 3: ...3 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Страница 9: ...Preface 9 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Страница 21: ...Contents 19 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Страница 35: ...1 Introduction 33 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Страница 365: ...2 Functions 363 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Страница 443: ...3 Mounting and Commissioning 441 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Страница 529: ...4 Technical Data 527 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Страница 699: ...A Appendix 697 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Страница 701: ...Literature 699 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Страница 714: ...Index 712 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Страница 715: ...Index 713 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...