3.1 Mounting and Connections
412
SIPROTEC 4, 7SJ62/63/64 Handbuch
C53000-G1140-C147-A, Edition 07.2015
3.1.3.4
Mounting with Detached Operator Panel
Caution!
Be careful when removing or plugging the connector between device and de-
tached operator panel
Non–observance of the following measure can result in property damage. Without the
cable the device is not ready for operation!
Do never pull or plug the connector between the device and the detached operator
panel during operation while the device is alive!
For mounting the
device
proceed as follows:
• Fasten device of housing size
1
/
2
with 6 screws and device of housing size
1
/
1
with
10 screws. For dimensions see for the Technical Data, Section 4.26.
• Connect the ground on the rear plate of the device to the protective ground of the
panel. Using at least one M4 screw. The cross-section of the line, here used, must
correspond to the maximum connected cross-section, at least 2.5 mm
2
.
• Connections are realized via the plug terminals or screw terminals on the rear side
of the device in accordance to the circuit diagram. When using forked lugs for direct
connections or screw terminal, the screws, before having inserted the lugs and
wires, must be tightened in such a way that the screw heads are even with the ter-
minal block. A ring lug must be centered in the connection chamber, in such a way
that the screw thread fits in the hole of the lug. The SIPROTEC 4 System Descrip-
tion provides information on wire size, lugs, bending radii, etc. which must be ob-
served.
For mounting the
operator panel
please observe the following:
• Remove the 4 covers on the corners of the front plate. Thus, 4 respectively elongat-
ed holes in the mounting bracket are revealed and can be accessed.
• Insert the operator panel into the panel cut-out and fasten with four screws. For di-
mensions see Technical Data.
• Replace the 4 covers.
• Connect the ground on the rear plate of the device to the protective ground of the
panel. Using at least one M4 screw. The cross-section of the line, here used, must
correspond to the maximum connected cross-section, at least 2.5 mm
2
.
• Connect the operator panel to the device. Furthermore, plug the 68-pin connector
of the cable belonging to the operator panel into the corresponding connection at
the rear side of the device (see SIPROTEC 4 System Description).
Содержание siprotec SJ62
Страница 3: ...3 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Страница 9: ...Preface 9 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Страница 21: ...Contents 19 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Страница 35: ...1 Introduction 33 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Страница 365: ...2 Functions 363 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Страница 443: ...3 Mounting and Commissioning 441 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Страница 529: ...4 Technical Data 527 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Страница 699: ...A Appendix 697 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Страница 701: ...Literature 699 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Страница 714: ...Index 712 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...
Страница 715: ...Index 713 SIPROTEC 4 7SJ62 63 64 Handbuch C53000 G1140 C147 A Edition 07 2015 ...