Message
No.
Meaning
see
Section
par too high:
30068
Parameter setting value too high for the indicated address number
settingFault:
30069
Parameter setting implausible for the indicated address number
Diff
Adap.fact.
5620
The matching factor of the current transformers for the differential
protection is too great or too small
2.1.4 Power
System Data
1
2.2 Differen-
tial Protec-
tion
Diff err. Set.
5623
Differential protection setting not plausible
REF Not avail.
199.2491
Restricted earth fault protection is not available for the configured
protected object
REF Adap.fact.
199.2494
The matching factor of the current transformers for restricted earth
fault protection is too great or too small.
2.1.4 Power
System Data
1
2.3 Restricte
d Earth Fault
Protection
REF Err CTstar
199.2492
There is no single-phase measuring input assigned to the starpoint
current for restricted earth fault protection
2.1.4 Power
System Data
1
2.2 Differen-
tial Protec-
tion
REF2 Not avail.
205.2491
Restricted earth fault protection 2 is not available for the configured
protected object
REF2 Adap.fact.
205.2494
The matching factor of the current transformers for restricted earth
fault protection 2 is too great or too small.
2.4.1 Gener
al
2.3 Restricte
d Earth Fault
Protection
REF2 Err CTstar
205.2492
There is no single-phase measuring input assigned to the starpoint
current for restricted earth fault protection 2
2.4.1 Gener
al
2.2 Differen-
tial Protec-
tion
O/C Ph. Not av.
023.2491
Time overcurrent protection for phase currents is not available for the
configured protected object
O/C Ph2 Not av.
207.2491
Time overcurrent protection for phase currents 2 is not available for
the configured protected object
2.1.4 Power
System Data
12.1.6 Powe
r System
Data 2
O/C Ph3 Not av.
209.2491
Time overcurrent protection for phase currents 3 is not available for
the configured protected object
2.1.4 Power
System Data
12.1.6 Powe
r System
Data 2
Mounting and Commissioning
3.3 Commissioning
SIPROTEC 4, 7UT6x, Manual
361
C53000-G1176-C230-5, Edition 09.2016
Содержание SIPROTEC 4 7UT6 Series
Страница 394: ...394 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Страница 482: ...482 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Страница 504: ...504 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Страница 522: ...522 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Страница 528: ...528 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Страница 538: ...538 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Страница 664: ...664 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Страница 666: ...666 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Страница 683: ...Z Zero sequence currents 109 Index SIPROTEC 4 7UT6x Manual 683 C53000 G1176 C230 5 Edition 09 2016 ...
Страница 684: ...684 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...