[diff-trafo-erdkurzschuss-beisp1-020926-st, 1, en_GB]
Figure 2-29
Example for an earth fault outside a transformer with current distribution
The complete matrix equation for the earthed side (right) is in this case, including all in-flowing currents:
[diff-trafo-erdkurzschluss-021026-rei, 1, en_GB]
Ι
SP
corresponds to –3
Ι
0
in case of through-flowing current. The zero sequence current is included in case of an
internal fault (from
Ι
0
=
1
/
3
Ι
SP
), in case of an external earth fault, the zero sequence current component of the
line currents 3 ·
Ι
0
= (
Ι
L1
+
Ι
L2
+
Ι
L3
) (negative here) is compensated by the starpoint current
Ι
SP
. In this way,
almost full sensitivity (with zero sequence current) is achieved for internal earth faults and full elimination of
the zero sequence current in case of external earth faults. For consideration of the earth fault current, the
advanced parameter diff protection with measured earth current, side x must be switched on (addresses 1211
DIFFw.IE1-MEAS
to 1215
DIFFw.IE5-MEAS
=
YES
).
Even higher earth fault sensitivity during internal earth fault is possible by means of the restricted earth fault
protection (Section
2.3 Restricted Earth Fault Protection
).
Starpoint Current not Available
In many cases, however, the starpoint current is not available. The total summation of the in-flowing currents
is thus not possible because
Ι
SP
is missing. In order to avoid false formation of the differential current, the zero
sequence current must be eliminated from the line currents (–
Ι
L3
= –3 ·
Ι
0
).
shows an example of a YNd5 vector group with earthed starpoint on the Y-side.
In
on the left side, the zero sequence currents cancel each other because of the calculation of the
current differences. This complies with the fact that zero sequence current is not possible outside the delta
winding. On the right side, the zero sequence current must be eliminated if the starpoint current cannot be
included. This results from the matrix equation, e.g. for
Ι
A
:
1
/
3
· (2
Ι
L1
– 1
Ι
L2
– 1
Ι
L3
) =
1
/
3
· (3
Ι
L1
–
Ι
L1
–
Ι
L2
–
Ι
L3
) =
1
/
3
· (3
Ι
L1
– 3
Ι
0
) = (
Ι
L1
–
Ι
0
).
Zero sequence current elimination achieves that fault currents which flow via the transformer during earth
faults in the network in case of an earth point in the protected zone (transformer starpoint or starpoint former
by neutral earth reactor) are rendered harmless without any special external measures. Refer e.g. to
: Because of the earthed starpoint, a zero sequence current occurs on the right side during a
network fault but not on the left side. Comparison of the phase currents, without zero sequence current elimi-
nation and without inclusion of the starpoint current, would cause a wrong result (current difference in spite
of an external fault).
Functions
2.2 Differential Protection
104
SIPROTEC 4, 7UT6x, Manual
C53000-G1176-C230-5, Edition 09.2016
Содержание SIPROTEC 4 7UT6 Series
Страница 394: ...394 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Страница 482: ...482 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Страница 504: ...504 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Страница 522: ...522 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Страница 528: ...528 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Страница 538: ...538 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Страница 664: ...664 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Страница 666: ...666 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Страница 683: ...Z Zero sequence currents 109 Index SIPROTEC 4 7UT6x Manual 683 C53000 G1176 C230 5 Edition 09 2016 ...
Страница 684: ...684 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...