At address 7612
DMD Sync.Time
it can be determined whether the point in time for averaging selected
under address 7611 is to commence on the hour (
On The Hour
) or is to be synchronised with another point
in time (
15 After Hour
,
30 After Hour
or
45 After Hour
).
If the settings for averaging are changed, then the measured values stored in the buffer are deleted, and new
results for the average calculation are only available after the set time period has passed.
Settings
Addr.
Parameter
Setting Options
Default Setting
Comments
7611
DMD Interval
15 Min., 1 Sub
15 Min., 3 Subs
15 Min.,15 Subs
30 Min., 1 Sub
60 Min., 1 Sub
60 Min.,10 Subs
5 Min., 5 Subs
60 Min., 1 Sub
Demand Calculation Intervals
7612
DMD Sync.Time
On The Hour
15 After Hour
30 After Hour
45 After Hour
On The Hour
Demand Synchronization Time
Min/Max Measurement Setup
Setting Notes
Resetting of the minimum and maximum values can also be done cyclically, commencing with the preselected
starting time. To select this feature, address 7621
MinMax cycRESET
should be set to
YES
. The point in time
when reset is to take place (the minute of the day in which reset will take place) is set at address 7622
MiMa
RESET TIME
. The reset cycle in days is entered at address 7623
MiMa RESETCYCLE
, and the beginning date
of the cyclical process, from the time of the setting procedure (in days), is entered at address 7624
MinMaxRES.START
.
Settings
Addr.
Parameter
Setting Options
Default Setting
Comments
7621
MinMax cycRESET
NO
YES
YES
Automatic Cyclic Reset Function
7622
MiMa RESET TIME
0 .. 1439 min
0 min
MinMax Reset Timer
7623
MiMa RESETCYCLE
1 .. 365 Days
7 Days
MinMax Reset Cycle Period
7624
MinMaxRES.START
1 .. 365 Days
1 Days
MinMax Start Reset Cycle in
Information List
No.
Information
Type of
Informa-
tion
Comments
-
ResMinMax
IntSP_Ev
Reset Minimum and Maximum counter
11001
>Reset MinMax
SP
>Reset MinMaxValues
2.23.1.2
2.23.2
2.23.2.1
2.23.2.2
2.23.2.3
Functions
2.23 Average Values, Minimum and Maximum Values
302
SIPROTEC 4, 7UT6x, Manual
C53000-G1176-C230-5, Edition 09.2016
Содержание SIPROTEC 4 7UT6 Series
Страница 394: ...394 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Страница 482: ...482 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Страница 504: ...504 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Страница 522: ...522 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Страница 528: ...528 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Страница 538: ...538 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Страница 664: ...664 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Страница 666: ...666 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Страница 683: ...Z Zero sequence currents 109 Index SIPROTEC 4 7UT6x Manual 683 C53000 G1176 C230 5 Edition 09 2016 ...
Страница 684: ...684 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...