Monitoring
Possible Causes
Malfunction
Response
Indication (No.)
Output
Measured value acquisi-
tion
Internal (converter or
sampling)
Protection out of oper-
ation,
Alarm
LED “ERROR”
Error MeasurSys
DOK
2)
drops
out
Internal (offset)
Protection out of oper-
ation,
Alarm
LED “ERROR”
Error Offset
DOK
2)
drops
out
Hardware-Watchdog
Internal (processor
failure)
Device out of opera-
tion
LED “ERROR”
DOK
2)
drops
out
Software-Watchdog
Internal (program flow)
Restart attempt
1)
LED “ERROR”
DOK
2)
drops
out
Working memory
Internal (RAM)
Restart attempt
1)
,
restart aborted
Device out of opera-
tion
LED flashes
DOK
2)
drops
out
Program memory
Internal (EPROM)
Restart attempt
1)
LED “ERROR”
DOK
2)
drops
out
Parameter memory
Internal (EEPROM or
RAM)
Restart attempt
1)
LED “ERROR”
DOK
2)
drops
out
1 A/5 A/0.1 A setting
Jumper setting 1/5/0.1 A
wrong
Alarms,
Protection out of oper-
ation
Error1A/5Awrong
LED “ERROR”
DOK
2)
drops
out
Calibration data
Internal
(device not calibrated)
Alarm,
Using default values
Alarm adjustm.
as allocated
Backup battery
Internal (backup battery) Alarm
Fail Battery
as allocated
Clock
Time synchronization
Alarm
Clock SyncError
as allocated
P.C.B. modules
Module does not comply
with ordering number
Alarms,
Protection out of oper-
ation
Error Board 0
...
Error Board 7
und
ggf.
Error MeasurSys
DOK
2)
drops
out
Interfaces
Faulty interface
Alarm
Err. Module B
...
Err. Module D
as allocated
RTD box connection
RTD box not connected or
number does not match
No overload protec-
tion;
Alarm
Fail: RTD-Box 1
or
Fail: RTD-Box 2
as allocated
Current balance
External (system or
current transformers)
Alarm with identifica-
tion of the measuring
location
Fail balan. IM1
or
Fail balan. IM2
Fail I balance
as allocated
Voltage sum
Internal
Measured value acquisi-
tion
Alarm
Fail Σ U Ph-E
as allocated
Voltage balance
external (system or
voltage transformer)
Alarm
Fail U balance
as allocated
Phase sequence
External (system or
connections)
Alarm with identifica-
tion of the measuring
location
FailPh.Seq IM1
...
FailPh.Seq IM5
Fail Ph. Seq. I
Fail Ph. Seq. U
as allocated
Functions
2.19 Monitoring Functions
SIPROTEC 4, 7UT6x, Manual
269
C53000-G1176-C230-5, Edition 09.2016
Содержание SIPROTEC 4 7UT6 Series
Страница 394: ...394 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Страница 482: ...482 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Страница 504: ...504 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Страница 522: ...522 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Страница 528: ...528 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Страница 538: ...538 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Страница 664: ...664 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Страница 666: ...666 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Страница 683: ...Z Zero sequence currents 109 Index SIPROTEC 4 7UT6x Manual 683 C53000 G1176 C230 5 Edition 09 2016 ...
Страница 684: ...684 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...