![Siemens SIPROTEC 4 7UT6 Series Скачать руководство пользователя страница 141](http://html.mh-extra.com/html/siemens/siprotec-4-7ut6-series/siprotec-4-7ut6-series_manual_382658141.webp)
For the zero sequence current
3I0p
the characteristic can be selected independently of the characteristic used
for the phase currents.
The pickup values of the stages
Ip
(phases) and
3I0p
(zero sequence current) and the time multipliers valid
for each of these states can be set individually.
show the logic diagrams of the inverse overcurrent time protection for phase
currents
Ip
and for the zero sequence currents
3I0p
.
[logik-umz-abh-amz-phasenstrom-iec-kennlinie-121102-st, 1, en_GB]
Figure 2-71
Logic diagram of the inverse overcurrent protection for phase currents — example of IEC char-
acteristic (simplified)
Functions
2.4 Time Overcurrent Protection for Phase and Residual Currents
SIPROTEC 4, 7UT6x, Manual
141
C53000-G1176-C230-5, Edition 09.2016
Содержание SIPROTEC 4 7UT6 Series
Страница 394: ...394 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Страница 482: ...482 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Страница 504: ...504 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Страница 522: ...522 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Страница 528: ...528 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Страница 538: ...538 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Страница 664: ...664 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Страница 666: ...666 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Страница 683: ...Z Zero sequence currents 109 Index SIPROTEC 4 7UT6x Manual 683 C53000 G1176 C230 5 Edition 09 2016 ...
Страница 684: ...684 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...