The pickup value (0.1 A or 0.05 A in the example) is set in address 2706
1Phase I>
. The
Ι
>> stage is not
required (address 2703
1Phase I>>
= ∞).
The trip command can be delayed under address 2707
T 1Phase I>
. This time delay is usually set to 0.
If a higher number of current transformers is connected in parallel, e.g. when using as busbar protection with
several feeders, the magnetising currents of the transformers connected in parallel cannot be neglected
anymore. In this case, the sum total of the magnetising currents at half knee-point voltage (corresponding to
the setting value) has to be established. These magnetising currents reduce the current through the resistor R.
The actual pickup value thus increases accordingly.
Use as Tank Leakage Protection
If the single-phase time overcurrent protection is used as tank leakage protection, only the pickup value for
the respective 1-phase current input is set on 7UT6x.
The tank leakage protection is a highly sensitive overcurrent protection which detects the leakage current
between the isolated transformer tank and earth. Its sensitivity is set in address 2706
1Phase I>
. Stage
Ι
>>
is not used (address 2703
1Phase I>>
= ∞).
The trip command can be delayed in address 2707
T 1Phase I>
. Normally, this delay time is set to
0
.
i
i
NOTE
In the following parameter overview the addresses 2703 and 2706 apply to a high-sensitive current meas-
uring input and are independent from the rated current.
Settings
The table indicates region-specific presettings. Column C (configuration) indicates the corresponding secon-
dary nominal current of the current transformer.
Addr.
Parameter
C
Setting Options
Default Setting
Comments
2701
1Phase O/C
OFF
ON
Block relay
OFF
1Phase Time Overcurrent
2702
1Phase I>>
1A
0.05 .. 35.00 A; ∞
0.50 A
1Phase O/C I>> Pickup
5A
0.25 .. 175.00 A; ∞
2.50 A
2703
1Phase I>>
0.003 .. 1.500 A; ∞
0.300 A
1Phase O/C I>> Pickup
2704
T 1Phase I>>
0.00 .. 60.00 sec; ∞
0.10 sec
T 1Phase O/C I>> Time
Delay
2705
1Phase I>
1A
0.05 .. 35.00 A; ∞
0.20 A
1Phase O/C I> Pickup
5A
0.25 .. 175.00 A; ∞
1.00 A
2706
1Phase I>
0.003 .. 1.500 A; ∞
0.100 A
1Phase O/C I> Pickup
2707
T 1Phase I>
0.00 .. 60.00 sec; ∞
0.50 sec
T 1Phase O/C I> Time Delay
Information List
No.
Information
Type of
Informa-
tion
Comments
200.2404 >BLK 1Ph. O/C
SP
>BLOCK Time Overcurrent 1Phase
200.2411 O/C 1Ph. OFF
OUT
Time Overcurrent 1Phase is OFF
200.2412 O/C 1Ph. BLK
OUT
Time Overcurrent 1Phase is BLOCKED
200.2413 O/C 1Ph. ACT
OUT
Time Overcurrent 1Phase is ACTIVE
200.2421 O/C 1Ph PU
OUT
Time Overcurrent 1Phase picked up
2.7.5
2.7.6
Functions
2.7 Single-Phase Time Overcurrent Protection
SIPROTEC 4, 7UT6x, Manual
185
C53000-G1176-C230-5, Edition 09.2016
Содержание SIPROTEC 4 7UT6 Series
Страница 394: ...394 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Страница 482: ...482 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Страница 504: ...504 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Страница 522: ...522 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Страница 528: ...528 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Страница 538: ...538 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Страница 664: ...664 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Страница 666: ...666 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Страница 683: ...Z Zero sequence currents 109 Index SIPROTEC 4 7UT6x Manual 683 C53000 G1176 C230 5 Edition 09 2016 ...
Страница 684: ...684 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...