NOTE
When configuring the topology proceed exactly in the order given below. Some of the following settings
and setting possibilities depend on settings performed before. In DIGSI the tabs (setting sheets) under
Power System Data 1 should be edited from the left tab to the right.
First of all, number the sides of the main protected object consecutively, next number the measuring loca-
tions, beginning with those for the main object, then for the remaining. In the example (
) there are
2 sides
S1
and
S2
, the 5 measuring locations are
M1
to
M5
.
The following sequence of sides is advised:
•
For power transformers, start with the higher voltage side, as well for generator/transformer units or
motor/transformer units.
•
For auto-transformers, the common winding must be declared as side 1 and side 2, further taps shall
follow (if applicable), then a delta winding (if applicable). Side 5 is not permitted here.
•
For generators, start with the terminal side.
•
For motors and shunt reactors, start with the current supply side.
•
For series reactors, lines, and busbars, there is no preferred side.
Side determination plays an important role for all of the following settings.
Proceed to number the measuring locations, beginning with those which are assigned to the main protected
object. Take the order of side numbering, next the non-assigned measuring locations (if used). Refer also to
Proceed numbering the auxiliary measuring locations (1-phase), again in the order: assigned locations and
then further (if used).
i
i
NOTE
The determination of the sides and measuring locations is imperative for all further setting steps. It is also
important that the currents from the measuring locations (current transformers) are connected to the asso-
ciated analogue current inputs of the device: The currents of measuring location M1 must be connected to
the device at measuring locations
Ι
L1M1
,
Ι
L2M1
,
Ι
L3M1
(in single-phase transformers
Ι
L2M1
), is omitted!
The topological data can be altered only with a PC using DIGSI.
Global Data for 3-Phase Measuring Locations
Determine the total number of 3-phase current measuring locations (= connected current transformer sets)
which are connected to the device. Enter this number in address 211
No Conn.MeasLoc
(number of meas-
uring locations connected). 7UT612 allows a maximum number of 2, 7UT613 and 7UT633 allow a maximum
number of 3, 7UT635 a maximum of 5 measuring locations. The examples in
contain 5 measuring locations each.
The number of 3-phase measuring locations assigned to the main protected object are set in address 212
No
AssigMeasLoc
(number of assigned measuring locations). Of course, this number cannot be higher than
that of address 211. The difference
No Conn.MeasLoc
–
No AssigMeasLoc
is the number of non-assigned
three-phase measuring locations. Both examples in
and
show five of the four assigned 3-
phase measuring locations:
M1
to
M4
.
M5
is a non-assigned measuring location.
The number of sides associated with the main protected object is set in address 213
NUMBER OF SIDES
. In
the example
, the protected object is a power transformer with 2 windings; the number of sides is 2:
, the main protected object is a power transformer with 3 windings; the
number of sides is
3
. In case of an auto-transformer, a maximum of 4 sides is permissible (see below).
Of course, the number of sides can be equal to the number of measuring locations (but never greater). The
example in
shows a three-winding power transformer with one set of current transformers at each
side. In this example:
No AssigMeasLoc
=
3
and
NUMBER OF SIDES
=
3
.
No distinction between sides and measuring locations is made in case of a busbar. Both correspond to the
feeders. Therefore, address 213 is missing if address 105
PROT. OBJECT
=
3ph Busbar
has been set.
Functions
2.1 General
44
SIPROTEC 4, 7UT6x, Manual
C53000-G1176-C230-5, Edition 09.2016
Содержание SIPROTEC 4 7UT6 Series
Страница 394: ...394 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Страница 482: ...482 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Страница 504: ...504 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Страница 522: ...522 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Страница 528: ...528 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Страница 538: ...538 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Страница 664: ...664 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Страница 666: ...666 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Страница 683: ...Z Zero sequence currents 109 Index SIPROTEC 4 7UT6x Manual 683 C53000 G1176 C230 5 Edition 09 2016 ...
Страница 684: ...684 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...