Addr. Parameter
Function
C
Setting Options
Default Setting
Comments
1243A SLOPE 2
Diff. Prot
0.25 .. 0.95
0.50
Slope 2 of Tripping Char-
acteristic
1244A BASE POINT 2
Diff. Prot
0.00 .. 10.00 I/InO
2.50 I/InO
Base Point for Slope 2 of
Charac.
1251A I-REST. STARTUP
Diff. Prot
0.00 .. 2.00 I/InO
0.10 I/InO
I-RESTRAINT for Start
Detection
1252A START-FACTOR
Diff. Prot
1.0 .. 2.0
1.0
Factor for Increasing of
Char. at Start
1253 T START MAX
Diff. Prot
0.0 .. 180.0 sec
5.0 sec
Maximum Permissible
Starting Time
1261A I-ADD ON STAB.
Diff. Prot
2.00 .. 15.00 I/InO
4.00 I/InO
Pickup for Add-on Stabili-
zation
1262A T ADD ON-STAB.
Diff. Prot
2 .. 250 Cycle; ∞
15 Cycle
Duration of Add-on Stabi-
lization
1263A CROSSB. ADD ON
Diff. Prot
2 .. 1000 Cycle; 0; ∞ 15 Cycle
Time for Cross-blocking
Add-on Stabiliz.
1271 2. HARMONIC
Diff. Prot
10 .. 80 %
15 %
2nd Harmonic Content in
I-DIFF
1272A CROSSB. 2. HARM
Diff. Prot
2 .. 1000 Cycle; 0; ∞ 3 Cycle
Time for Cross-blocking
2nd Harm.
1276 n. HARMONIC
Diff. Prot
10 .. 80 %
30 %
n-th Harmonic Content in
I-DIFF
1277A CROSSB. n.HARM
Diff. Prot
2 .. 1000 Cycle; 0; ∞ 0 Cycle
Time for Cross-blocking n-
th Harm.
1278A IDIFFmax n.HM
Diff. Prot
0.5 .. 20.0 I/InO
1.5 I/InO
Limit IDIFFmax of n-th
Harm.Restraint
1281 I-DIFF> MON.
Diff. Prot
0.15 .. 0.80 I/InO
0.20 I/InO
Pickup Value of diff.
Current Monitoring
1282 T I-DIFF> MON.
Diff. Prot
1 .. 10 sec
2 sec
T I-DIFF> Monitoring Time
Delay
1283A Inst. Idiff Rec
Diff. Prot
NO
YES
NO
Fault record with inst. diff
current
1300 Blocked w. CWA
Diff. Prot
ON
OFF
ON
Blocking with CWA
1301 REF PROT.
REF
OFF
ON
Block relay
OFF
Restricted Earth Fault
Protection
1311 I-REF>
REF
0.05 .. 2.00 I/InS
0.15 I/InS
Pick up value I REF>
1312A T I-REF>
REF
0.00 .. 60.00 sec; ∞ 0.00 sec
T I-REF> Time Delay
1313A SLOPE
REF
0.00 .. 0.95
0.00
Slope of Charac. I-REF> =
f(I-SUM)
1401 REF PROT.
REF 2
OFF
ON
Block relay
OFF
Restricted Earth Fault
Protection
1411 I-REF>
REF 2
0.05 .. 2.00 I/InS
0.15 I/InS
Pick up value I REF>
1412A T I-REF>
REF 2
0.00 .. 60.00 sec; ∞ 0.00 sec
T I-REF> Time Delay
1413A SLOPE
REF 2
0.00 .. 0.95
0.00
Slope of Charac. I-REF> =
f(I-SUM)
1701 COLDLOAD PICKUP ColdLoadPickup
OFF
ON
OFF
Cold-Load-Pickup Func-
tion
Functions, Settings, Information
F.2 Settings
SIPROTEC 4, 7UT6x, Manual
563
C53000-G1176-C230-5, Edition 09.2016
Содержание SIPROTEC 4 7UT6 Series
Страница 394: ...394 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Страница 482: ...482 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Страница 504: ...504 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Страница 522: ...522 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Страница 528: ...528 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Страница 538: ...538 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Страница 664: ...664 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Страница 666: ...666 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Страница 683: ...Z Zero sequence currents 109 Index SIPROTEC 4 7UT6x Manual 683 C53000 G1176 C230 5 Edition 09 2016 ...
Страница 684: ...684 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...