Unbalanced Load Protection
Characteristics
Definite-time stages
DT
Ι
2
>>,
Ι
2
>
Inverse time stages
(acc. to IEC or ANSI)
IT
Ι
2P
One of the characteristics shown in
can be selected
Reset characteristics
with disk emulation
IT
For illustrations of possible reset time charac-
teristics see
on
the left-hand side.
Operating Range
0.1 to 4
Ι
/
Ι
nS
Current Stages
High current stage
Ι
2
>>
0.10 A to 3.00 A
1)
Increments 0.01 A
T
Ι
2
>>
0.00 s to 60.00 s
or ∞ (no trip)
Increments 0.01 s
Definite time current element
(50Ns- 2, 50Ns-1)
Ι
2
>
0.10 A to 3.00 A
1)
Increments 0.01 A
T
Ι
2
>
0.00 s to 60.00 s
or ∞ (no trip)
Increments 0.01 s
Inverse current element (51Ns-
IEC)
Ι
2P
0.10 A to 2.00 A
1)
Increments 0.01 A
T
Ι
2P
0.05 s to 3.20 s
or ∞ (no trip)
Increments 0.01 s
Inverse current element (51Ns-
ANSI)
Ι
2P
0.10 A to 2.00 A
1)
Increments 0.01 A
D
Ι
2P
0.50 s to 15.00 s
or ∞ (no trip)
Increments 0.01 s
Tolerances with inverse time
2)
Currents
3 % of setting value or 1 % nominal current
Times
1 % of setting value or 10 ms
Tolerances with definite time (IEC)
2)
Currents
Pickup
at
1.05 ≤
Ι
2
/
Ι
2P
≤ 1.15
Times
5 % ± 15 ms
5 % ± 45 ms
at f
N
= 50/60 Hz
at f
N
= 16.7 Hz
(only 7UT613/63x)
for 2 ≤
Ι
2
/
Ι
2P
≤ 20
and T
Ι
2P
/s ≥ 1
Tolerances with definite time (ANSI)
2)
Times
5 % ± 15 ms
5 % ± 45 ms
bei f
N
= 50/60 Hz
bei f
N
= 16.7 Hz
(only 7UT613/63x)
for 2 ≤
Ι
2
/
Ι
2P
≤ 20
and D
Ι
2P
/s ≥ 1
The set times are pure delay times.
1)
Secondary values for
Ι
N
= 1 A; bei
Ι
N
= 5 A the currents must be multiplied by 5.
2)
For one 3-phase measuring location
4.8
Technical Data
4.8 Unbalanced Load Protection
432
SIPROTEC 4, 7UT6x, Manual
C53000-G1176-C230-5, Edition 09.2016
Содержание SIPROTEC 4 7UT6 Series
Страница 394: ...394 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Страница 482: ...482 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Страница 504: ...504 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Страница 522: ...522 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Страница 528: ...528 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Страница 538: ...538 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Страница 664: ...664 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Страница 666: ...666 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Страница 683: ...Z Zero sequence currents 109 Index SIPROTEC 4 7UT6x Manual 683 C53000 G1176 C230 5 Edition 09 2016 ...
Страница 684: ...684 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...