Addr.
Parameter
Setting Options
Default Setting
Comments
1213A
DIFFw.IE3-MEAS
NO
YES
NO
Diff-Prot. with meas. Earth Current
S3
1214A
DIFFw.IE4-MEAS
NO
YES
NO
Diff-Prot. with meas. Earth Current
S4
1215A
DIFFw.IE5-MEAS
NO
YES
NO
Diff-Prot. with meas. Earth Current
S5
1216A
DIFFw.IE3phMEAS
NO
YES
NO
Diff-Prot.with meas.current
earth.electr
1221
I-DIFF>
0.05 .. 2.00 I/InO
0.20 I/InO
Pickup Value of Differential Curr.
1226A
T I-DIFF>
0.00 .. 60.00 sec; ∞
0.00 sec
T I-DIFF> Time Delay
1231
I-DIFF>>
0.5 .. 35.0 I/InO; ∞
7.5 I/InO
Pickup Value of High Set Trip
1236A
T I-DIFF>>
0.00 .. 60.00 sec; ∞
0.00 sec
T I-DIFF>> Time Delay
1241A
SLOPE 1
0.10 .. 0.50
0.25
Slope 1 of Tripping Characteristic
1242A
BASE POINT 1
0.00 .. 2.00 I/InO
0.00 I/InO
Base Point for Slope 1 of Charac.
1243A
SLOPE 2
0.25 .. 0.95
0.50
Slope 2 of Tripping Characteristic
1244A
BASE POINT 2
0.00 .. 10.00 I/InO
2.50 I/InO
Base Point for Slope 2 of Charac.
1251A
I-REST. STARTUP
0.00 .. 2.00 I/InO
0.10 I/InO
I-RESTRAINT for Start Detection
1252A
START-FACTOR
1.0 .. 2.0
1.0
Factor for Increasing of Char. at
Start
1253
T START MAX
0.0 .. 180.0 sec
5.0 sec
Maximum Permissible Starting
Time
1261A
I-ADD ON STAB.
2.00 .. 15.00 I/InO
4.00 I/InO
Pickup for Add-on Stabilization
1262A
T ADD ON-STAB.
2 .. 250 Cycle; ∞
15 Cycle
Duration of Add-on Stabilization
1263A
CROSSB. ADD ON
2 .. 1000 Cycle; 0; ∞
15 Cycle
Time for Cross-blocking Add-on
Stabiliz.
1271
2. HARMONIC
10 .. 80 %
15 %
2nd Harmonic Content in I-DIFF
1272A
CROSSB. 2. HARM
2 .. 1000 Cycle; 0; ∞
3 Cycle
Time for Cross-blocking 2nd Harm.
1276
n. HARMONIC
10 .. 80 %
30 %
n-th Harmonic Content in I-DIFF
1277A
CROSSB. n.HARM
2 .. 1000 Cycle; 0; ∞
0 Cycle
Time for Cross-blocking n-th
Harm.
1278A
IDIFFmax n.HM
0.5 .. 20.0 I/InO
1.5 I/InO
Limit IDIFFmax of n-th
Harm.Restraint
1281
I-DIFF> MON.
0.15 .. 0.80 I/InO
0.20 I/InO
Pickup Value of diff. Current Moni-
toring
1282
T I-DIFF> MON.
1 .. 10 sec
2 sec
T I-DIFF> Monitoring Time Delay
1283A
Inst. Idiff Rec
NO
YES
NO
Fault record with inst. diff current
1300
Blocked w. CWA
ON
OFF
ON
Blocking with CWA
Information List
No.
Information
Type of
Informa-
tion
Comments
5603
>Diff BLOCK
SP
>BLOCK differential protection
5615
Diff OFF
OUT
Differential protection is switched OFF
5616
Diff BLOCKED
OUT
Differential protection is BLOCKED
2.2.9
Functions
2.2 Differential Protection
122
SIPROTEC 4, 7UT6x, Manual
C53000-G1176-C230-5, Edition 09.2016
Содержание SIPROTEC 4 7UT6 Series
Страница 394: ...394 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Страница 482: ...482 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Страница 504: ...504 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Страница 522: ...522 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Страница 528: ...528 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Страница 538: ...538 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Страница 664: ...664 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Страница 666: ...666 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Страница 683: ...Z Zero sequence currents 109 Index SIPROTEC 4 7UT6x Manual 683 C53000 G1176 C230 5 Edition 09 2016 ...
Страница 684: ...684 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...