with
P
sec
secondary power
U
Nprim
primary rated voltage of the voltage transformer (interlinked)
U
Nsec
secondary rated current of the voltage transformer (interlinked)
I
Nprim
primary rated current of the current transformer
I
Nsec
secondary rated current of the current transformer
P
prim
primary power
Example:
Transformer
16 MVA
(Winding)
20 kV
Current transformer
500 A/5 A
Voltage transformer
20 kV/100 V
Switching off during P<
10 % = 0.1
Connecting a parallel transformer
Parallel transformer during P>
90 % = 0.9
In case of reference setting (with reference to the sides = winding data)
Address 5112
P< fwd
= 0.10
Address 5115
P> fwd
= 0.90
When setting in watt secondary, this has the following effect
P< =
P> =
the setting values
Address 5111
Pf<
= 80 W
Address 5114
Pf>
= 720 W
Delay Times
The setting of the delay times depend on the application. In the example of transformer switchover or also in
case of generator switchover, a long delay (up to one minute = 60 s) will be set so that short-term load fluctu-
ations do not result in repeated switchover. In case of network splitting, short delays are permitted, which,
amongst others, must conform with the time grading of the short-circuit protective relays.
For undershooting of active power, address 5113
T-Pf<
applies and for the exceeding of active power
address 5116
T-Pf>
applies.
The set times are additional time delays that do not include the operating times (measuring time, dropout
time) of the monitoring function. Please note that averaging over 16 periods is executed during “precise”
measuring procedures; the operating time is thus respectively higher. If a delay time is set to
, this does not
result in a trip, however, the pickup will be indicated.
Measuring Procedure
The measuring procedure can be set at address 5117
MEAS. METHOD
. This parameter can only be set with
DIGSI under Additional Settings. The option
MEAS. METHOD
=
accurate
is mainly required if also small
active power from great apparent power must be calculated precisely, e.g. in generator range or in protected
objects with high reactive power. Please also note that the operating time in this option is higher due to aver-
aging over 16 periods. A precise measurement requires that the angle errors of the current and voltage trans-
formers are compensated by means of a respective setting of the fault angle in address 803
CORRECT. U
Functions
2.13 Forward Power Supervision
SIPROTEC 4, 7UT6x, Manual
231
C53000-G1176-C230-5, Edition 09.2016
Содержание SIPROTEC 4 7UT6 Series
Страница 394: ...394 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Страница 482: ...482 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Страница 504: ...504 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Страница 522: ...522 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Страница 528: ...528 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Страница 538: ...538 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Страница 664: ...664 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Страница 666: ...666 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Страница 683: ...Z Zero sequence currents 109 Index SIPROTEC 4 7UT6x Manual 683 C53000 G1176 C230 5 Edition 09 2016 ...
Страница 684: ...684 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...