Jumper
Rated voltage
DC 24 V to 48 V
DC 60 V to 125 V
DC 110 V to 250 V,
AC 115 V to 230 V
DC 220 V to 250 V,
AC 115 V to 230 V
X55
not used
not used
1-2
1-2
cannot be changed
interchangeable
Fuse
T4H250V
T2H250V
Table 3-6
Jumper setting of the Pickup Voltages of the binary inputs BI1 to BI5 on the C-CPU-2
processor module
Binary Inputs
Jumper
Threshold 19 V
1)
Threshold 88 V
2)
Threshold 176 V
3)
BI1
X21
1-2
2-3
3-4
BI2
X22
1-2
2-3
3-4
BI3
X23
1-2
2-3
3-4
BI4
X24
1-2
2-3
3-4
BI5
X25
1-2
2-3
3-4
1)
Factory settings for devices with rated power supply voltage DC 24 to 125 V
2)
Factory settings for devices with rated power supply voltage DC 110 to 220 V, AC 115 to 230 V to 250 V
3)
Only for control voltage DC 200 V or DC 250 V
Table 3-7
Jumper setting of the quiescent state of the Life Contact on the processor board C-CPU-2
Jumper
Open in the quiescent state
Closed in the quiescent state
Presetting
X40
1-2
2-3
2-3
By repositioning jumpers the interface RS485 can be modified into a RS232 interface and vice versa.
Jumpers X105 to X110 must be set to the same position!
Table 3-8
Jumper settings of the integrated RS232/RS485 Interface on the C-CPU-2 processor board
Jumper
RS232
RS485
X103 and X104
1-2
1-2
X105 to X110
1-2
2-3
The jumpers are preset at the factory according to the configuration ordered.
With interface RS232 jumper X111 is needed to activate CTS which enables the communication with the
modem.
Table 3-9
Jumper setting for CTS (Clear To Send, flow control) on the C-CPU-2 processor board
Jumper
/CTS from interface RS232
/CTS triggered by /RTS
X111
1-2
2-3
1)
1)
Delivery state
Jumper setting 2-3: The connection to the modem is usually established with a star coupler or fibre-optic
converter. Therefore the modem control signals according to RS232 standard DIN 66020 are not available.
Modem signals are not required since the connection to the SIPROTEC 4 devices is always operated in the half-
duplex mode. Please use the connection cable with order number 7XV5100-4.
Jumper setting 1-2: This setting makes the modem signals available, i. e. for a direct RS232-connection
between the SIPROTEC 4 device and the modem this setting can be selected optionally. We recommend to use
a standard RS232 modem connection cable (converter 9-pin to 25-pin).
Mounting and Commissioning
3.1 Mounting and Connections
SIPROTEC 4, 7UT6x, Manual
323
C53000-G1176-C230-5, Edition 09.2016
Содержание SIPROTEC 4 7UT6 Series
Страница 394: ...394 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Страница 482: ...482 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Страница 504: ...504 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Страница 522: ...522 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Страница 528: ...528 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Страница 538: ...538 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Страница 664: ...664 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Страница 666: ...666 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Страница 683: ...Z Zero sequence currents 109 Index SIPROTEC 4 7UT6x Manual 683 C53000 G1176 C230 5 Edition 09 2016 ...
Страница 684: ...684 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...