NEG
Negator
X
X
X
X
NOR
NOR - Gate
X
X
X
X
OR
OR - Gate
X
X
X
X
REAL_TO_DINT
Real after DoubleInt, adapter
X
X
X
X
REAL_TO_UINT
Real after U-Int, adapter
X
X
X
X
RISE_DETECT
Rising edge detector
X
X
X
X
RS_FF
RS- Flipflop
–
X
X
X
RS_FF_MEMO
Status memory for restart
X
X
X
X
SI_GET_STATUS
Information status single point
indication, decoder
X
X
X
X
SI_SET_STATUS
Single point indication with
status, encoder
X
X
X
X
SQUARE_ROOT
Root Extractor
X
X
X
X
SR_FF
SR- Flipflop
–
X
X
X
SR_FF_MEMO
Status memory for restart
X
X
X
X
ST_AND
AND gate with status
X
X
X
X
ST_NOT
Negator with status
X
X
X
X
ST_OR
OR gate with status
X
X
X
X
SUB
Substraction
X
X
X
X
TIMER
Timer
–
X
X
–
TIMER_SHORT
Simple timer
–
X
X
–
UINT_TO_REAL
U-Int to real, adapter
X
X
X
X
UPPER_SETPOINT
Upper Limit
X
–
–
–
X_OR
XOR - Gate
X
X
X
X
ZERO_POINT
Zero Supression
X
–
–
–
General Limits
Designation
Limit
Comments
Maximum number of all CFC charts consid-
ering all task levels
32
When the limit is exceeded, an error message is output by the
device. Consequently, the device is put into monitoring mode. The
red ERROR-LED lights up.
Maximum number of all CFC charts consid-
ering one task level
16
Only Error Message
(record in device fault log, evolving fault in processing procedure)
Maximum number of all CFC inputs consid-
ering all charts
400
When the limit is exceeded, an error message is output by the
device. Consequently, the device is put into monitoring mode. The
red ERROR-LED lights up.
Maximum number of inputs of one chart
for each task level (number of unequal
information items of the left border per task
level)
400
Only fault annunciation (record in device fault log); here the
number of elements of the left border per task level is counted.
Since the same information is indicated at the border several
times, only unequal information is to be counted.
Maximum number of reset-resistant flip-
flops
D_FF_MEMO
350
When the limit is exceeded, an error message is output by the
device. Consequently, the device is put into monitoring mode. The
red ERROR-LED lights up.
Device-specific Limits
Designation
Limit
Comments
Maximum number of synchronous changes
of chart inputs per task level
50
When the limit is exceeded, an error message is output by the
device. Consequently, the device is put into monitoring mode. The
red ERROR-LED lights up.
Maximum number of chart outputs per task
level
150
Technical Data
4.20 User-defined Functions (CFC)
SIPROTEC 4, 7UT6x, Manual
457
C53000-G1176-C230-5, Edition 09.2016
Содержание SIPROTEC 4 7UT6 Series
Страница 394: ...394 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Страница 482: ...482 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Страница 504: ...504 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Страница 522: ...522 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Страница 528: ...528 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Страница 538: ...538 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Страница 664: ...664 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Страница 666: ...666 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Страница 683: ...Z Zero sequence currents 109 Index SIPROTEC 4 7UT6x Manual 683 C53000 G1176 C230 5 Edition 09 2016 ...
Страница 684: ...684 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...