Circuit Breaker Failure Protection
Circuit Breaker Supervision
Current flow monitoring
0.04 A to 1.00 A
1)
for the respective side
Increments 0.01 A
Dropout-to-pickup ratio
approx. 0.9 für
Ι
≥ 0.25 A
1)
Tolerance
5 % of setting value or 0.01 A
1)
Breaker status monitoring
via circuit breaker auxiliary contacts and
binary input
1)
Secondary values based on
Ι
N
= 1 A; for
Ι
N
= 5 A the currents must be multiplied by 5.
Starting Conditions
For breaker failure protection
internal trip
external trip (via binary input)
Times
Pickup time for f
N
= 50/60 Hz
approx. 3 ms with measured quantities,
approx. 20 ms after switch-on of measured
quantities
Pickup time for f
N
= 16.7 Hz (nur
7UT613/63x)
approx. 60 ms after switch-on of measured
quantities
Dropout time for f
N
= 50/60 Hz
approx. 25 ms
Dropout time for f
N
= 16.7 Hz
(nur 7UT613/63x)
approx. 75 ms
Delay times
0.00 s to 60.00 s; ∞
Increments 0.01
Time tolerance
1 % of setting value or 10 ms
4.17
Technical Data
4.17 Circuit Breaker Failure Protection
SIPROTEC 4, 7UT6x, Manual
453
C53000-G1176-C230-5, Edition 09.2016
Содержание SIPROTEC 4 7UT6 Series
Страница 394: ...394 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Страница 482: ...482 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Страница 504: ...504 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Страница 522: ...522 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Страница 528: ...528 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Страница 538: ...538 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Страница 664: ...664 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Страница 666: ...666 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Страница 683: ...Z Zero sequence currents 109 Index SIPROTEC 4 7UT6x Manual 683 C53000 G1176 C230 5 Edition 09 2016 ...
Страница 684: ...684 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...