Maximum Distance of Transmission 3,280 ft or 1,000 m at ≤ 93.75 kBd
500 m or 1,640 ft at ≤ 187.5 kBd
200 m or 330 ft at ≤ 1.5 MBd
Profibus FO (FMS and DP)
FO connector type
ST connector
Single ring / double ring according to the order for FMS; for DP only
double ring available
Connection for flush-mounted
casing
Rear panel, mounting location “B”
Connection for surface-mounted
casing
in console housing on the case bottom via RS485 and external RS485/
optical converter
Transmission Speed
up to 1.5 MBd
1)
recommended:
> 500 kBd with normal casing
≤ 57 600 Bd at detached operator panel
Optical Wavelength
λ = 820 nm
Laser Class 1 according to EN
60825-1/-2
using glass fiber 50/125 μm or using glass fiber 62.5/125 μm
Permissible Optical Link Signal
Attenuation
max. 8 dB, with glass fiber 62.5/125 μm
Maximum Distance of Transmission max. 0.93 miles (1.5 km)
DNP3.0 / MODBUS RS485
Connection for flush-mounted
casing
Rear panel, mounting location “B”, 9-pin DSUB miniature connector
Connection for surface-mounted
casing
at the housing mounted case on the case bottom
Test Voltage
AC 500 V; 50 Hz
Transmission Speed
up to 19,200 Bd
1)
Maximum Distance of Transmission max. 0.62 miles (1 km)
DNP3.0 / MODBUS / FO
FO connector type
ST–Connector Receiver/Transmitter
Connection for flush-mounted
casing
Rear panel, mounting location “B”
Connection for surface-mounted
casing
not available
Transmission Speed
up to 19,200 Bd
1)
Optical Wavelength
λ = 820 nm
Laser Class 1 according to EN
60825-1/-2
using glass fiber 50/125 μm or using glass fiber 62.5/125 μm
Permissible Optical Link Signal
Attenuation
max. 8 dB, with glass fiber 62.5/125 μm
Maximum Distance of Transmission max. 0.93 miles (1.5 km)
Ethernet electrical (EN100) for DIGSI, IEC61850
Connection for flush-mounted
casing
rear panel, mounting location “B”; 2 x RJ45 socket contact 100BaseT acc.
to IEEE802.3
Connection for surface-mounted
casing
in console housing at case bottom
Technical Data
4.1 General
SIPROTEC 4, 7UT6x, Manual
401
C53000-G1176-C230-5, Edition 09.2016
Содержание SIPROTEC 4 7UT6 Series
Страница 394: ...394 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Страница 482: ...482 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Страница 504: ...504 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Страница 522: ...522 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Страница 528: ...528 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Страница 538: ...538 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Страница 664: ...664 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Страница 666: ...666 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Страница 683: ...Z Zero sequence currents 109 Index SIPROTEC 4 7UT6x Manual 683 C53000 G1176 C230 5 Edition 09 2016 ...
Страница 684: ...684 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...