![Siemens SIPROTEC 4 7UT6 Series Скачать руководство пользователя страница 92](http://html.mh-extra.com/html/siemens/siprotec-4-7ut6-series/siprotec-4-7ut6-series_manual_382658092.webp)
Differential Protection
The differential protection represents the main protection feature of the device. It is based on current compar-
ison under consideration of the transformation ratio of the transformer. 7UT6x is suitable for unit protection
of transformers, generators, motors, reactors, short lines, also with feeders, and (under observance of the
available number of current inputs) for busbar arrangements. Protection of generator/transformer units, trans-
former/ winding combinations or transformer/starpoint former, can also be realised. 7UT612 allows up to two,
7UT613 and 7UT633 allow up to 3, 7UT635 allows up to 5 three-phase measuring locations.
7UT6x can be used as a single-phase differential protection relay. In this case, 7UT612 allows up to 7, 7UT613
and 7UT633 allow up to 9, and 7UT635 up to 12 measuring locations, e.g. currents from a busbar with up to 7
or 9 or 12 feeders.
The protected zone is selectively limited by the CTs at its ends.
Functional Description of the Differential Protection
Processing of the measured values depends on the way the differential protection is used. This section
discusses first the differential protection function in general, regardless of the type of protected object. A
singlephase system is referred to. Particulars with regard to the individual protected objects follow thereafter.
Basic Principle with Two Sides
Differential protection is based on current comparison. It makes use of the fact that a protected object carries
always the same current i (dashed line in
) at its two sides in healthy operation. This current flows
into one side of the considered zone and leaves it again on the other side. A difference in currents is a clear
indication of a fault within this section. If the actual current transformation ratio is the same, the secondary
windings of the current transformers CT1 and CT2 at the sides of the protected object can be connected to
form a closed electric circuit with a secondary current I; a measuring element M, which is connected to the
electrical balance point, remains at zero current in healthy operation.
[diff-grundprinzip-020926-rei, 1, en_GB]
Figure 2-17
Basic principle of differential protection for two sides (single-phase illustration)
When a fault occurs in the zone limited by the transformers, a current i
1
+ i
2
, which is proportional to the fault
currents
Ι
1
+
Ι
2
flowing in from both sides is fed to the measuring element. As a result, the simple circuit
ensures a reliable tripping of the protection if the fault current flowing into the
protected zone during a fault is high enough for the measuring element M to respond.
All following considerations are based on the convention that all currents flowing into the protected zone are
defined as positive unless explicitly stated otherwise.
Basic Principle with more than Two Sides
For protected objects with three or more sides or for busbars, the differential principle is expanded in that the
total of all currents flowing into the protected object is zero in healthy operation, whereas in case of a fault
the total in-flowing current is equal to the fault current.
See
as an example for four feeders. The three-winding transformer in
has 4 measuring
locations, so it is treated by the differential protection like a “4-winding” transformer.
2.2
2.2.1
Functions
2.2 Differential Protection
92
SIPROTEC 4, 7UT6x, Manual
C53000-G1176-C230-5, Edition 09.2016
Содержание SIPROTEC 4 7UT6 Series
Страница 394: ...394 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Страница 482: ...482 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Страница 504: ...504 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Страница 522: ...522 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Страница 528: ...528 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Страница 538: ...538 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Страница 664: ...664 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Страница 666: ...666 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Страница 683: ...Z Zero sequence currents 109 Index SIPROTEC 4 7UT6x Manual 683 C53000 G1176 C230 5 Edition 09 2016 ...
Страница 684: ...684 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...